Plan Review Notes For Permit 17060812 |
Permit Number |
17060812 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-19 18:51:50 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF | | INSTALLATION AS REQUIRED BY FAC 61G20-3.001. FLORIDA | | PRODUCT APPROVAL FL5259-R25 SUBMITTED IS NOT FOR FLAT | | ROOF INSTALLATIONS. THIS PRODUCT APPROVAL IS FOR | | UNDERLAYMENTS FOR PITCHED ROOFS. | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM FLAT | | ROOF PRODUCT APPROVAL SUBMITTED IS GOING TO BE | | INSTALLED. IF THE SELECTED ASSEMBLY DOESN'T MEET THE | | DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND | | SEALED RAS 117 CALCULATIONS WILL BE REQUIRED TO MEET | | THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T ALLOW RAS 117 | | CALCULATIONS AND THE DESIGN PRESSURES DON'T MEET THE | | DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT CAN NOT BE | | USED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|