Plan Review Notes For Permit 17060797 |
Permit Number |
17060797 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-16 19:16:16 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- FLAT ROOF NOA 15-0622.21: THE DESIGN PRESSURES OF | | SELECTED ASSEMBLY ON PAGE 12 OF 19 OF NOA SUBMITTED | | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301.1 FBGC-RESIDENTIAL, 5TH | | EDITION (2014). | | | | 2- ACCORDING TO SKETCH SUBMITTED, THE SQUARE FOOTAGE OF | | FLAT ROOF IS MORE THAN ONE SQUARE. CLARIFY WHY DOING | | ONLY ONE SQUARE OF ROOFING. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected]. |
|