Plan Review Notes
Plan Review Notes For Permit 17060795
Permit Number 17060795
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-21 15:22:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060795
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: REFER TO NOTE #3 AND SHOW HOW THE
 EXISTING AC SYSTEMS WILL BE ALTERED TO PROVIDE
 SEPARATELY CONTROLLED, SEPARATELY ACCESSED, AND
 SEPARATELY BALANCED AIR FLOWS SYSTEMS TO EACH OF THE
 TWO TENANT SPACES.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]