Plan Review Notes For Permit 17060795 |
Permit Number |
17060795 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-20 16:07:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A 1 - THERE IS A ROOM WITH WALLS INDICATED | | WITHIN SUITE # 150 WITH NO DOOR. | | | | PLEASE REVIEW AND CLARIFY AND/OR CORRECT. PROVIDE A | | DOOR SCHEDULE AS APPLICABLE. | | | | | | | | 2) SHEET A 1 - THERE ARE INDICATIONS OF FIRE ALARM | | EQUIPMENT WORK. ANY FIRE ALARM EQUIPMENT WORK SHALL BE | | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | SAFETY CONTRACTORS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. | | | | | | 3) THE VALUE $ 600.00 ON THE APPLICATION APPEARS TO BE | | VERY LOW FOR THE AMOUNT OF WORK PROPOSED. | | | | PLEASE PROVIDE DETAILED AND ACCURATE VALUATION | | DOCUMENTS AND OR A COPY OF THE ACTUAL CONTRACT. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | | | |
|