Plan Review Notes
Plan Review Notes For Permit 17060795
Permit Number 17060795
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-20 16:07:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE IS A ROOM WITH WALLS INDICATED
 WITHIN SUITE # 150 WITH NO DOOR.
  
 PLEASE REVIEW AND CLARIFY AND/OR CORRECT. PROVIDE A
 DOOR SCHEDULE AS APPLICABLE.
  
  
  
 2) SHEET A 1 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT WORK. ANY FIRE ALARM EQUIPMENT WORK SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
 3) THE VALUE $ 600.00 ON THE APPLICATION APPEARS TO BE
 VERY LOW FOR THE AMOUNT OF WORK PROPOSED.
  
 PLEASE PROVIDE DETAILED AND ACCURATE VALUATION
 DOCUMENTS AND OR A COPY OF THE ACTUAL CONTRACT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  