2017-08-26 07:12:52 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060769 |
| ADD: 1560 PALM BEACH LAKES BLVD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 407-786-9724 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. AUGUST 26/ 2017 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. |
| |
| 3) 2ND REQUEST. RESPONSE, NOT YET SELECTED. THE SOILS |
| REPORTS BY UNIVERSAL ENGINEERING SCIENCES DATED AUGUST |
| 04/2016 UES REPORT NO. 13869 INDICATES THAT THREE SOILS |
| SAMPLES TEST RESULT INDICATE ORGANIC CONTENTS RANGED |
| FROM 10.7 TO 26.8 PERCENT AND MOISTURE CONTENTS RANGING |
| FROM 50.6 TO 121 PERCENT. ORGANIC SOILS (10 PERCENT OR |
| HIGHER) ENCOUNTERED IN STRUCTURAL AREAS SHOULD BE |
| REMOVED AND REPLACED WITH GOOD QUALITY FILL. PLEASE |
| PROVIDE WHICH SOILS ENGINEERING COMPANY WILL BE |
| OVERSEEING THE REMOVAL AND REPLACEMENT OF GOOD QUALITY |
| FILL IN ACCORDANCE TO THE SPECIFICATIONS AND PROCEDURES |
| OUTLINED IN THE SITE PREPARATION SECTION OF THIS |
| REPORT? 107.2.1.3 ADDITIONAL INFORMATION WILL BE |
| REQUIRED. 2014 FBC-B 1803.4 QUALIFIED REPRESENTATIVE. |
| |
| 4) 2ND REQUEST. RESPONSE, NOT YET SELECTED. RESIDENT |
| INSPECTOR 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| SERVICE IN THE FOLLOWING INSTANCES: |
| |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| INCH |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION BOLTED AND WELDED CONNECTIONS. |
| RESIDENT INSPECTOR WILL BE REQUIRED FROM FOUNDATION |
| THROUGH ROOF FRAMING, ROOF DECKING, WINDOW FRAME AND |
| GLAZING INSTALLATION. |
| |
| 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. |
| FORMS SENT TO: [email protected] 06/27/2017 97:15 AM |
| |
| 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED |
| |
| 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| 4E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND |
| GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP |
| DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT |
| APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED |
| TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF |
| DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY |
| OF THE ABOVE IS INSTALLED ON THE JOB. |
| |
| 4F) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 5) COMPLIED. |
| |
| 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP |
| VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY |
| GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT |
| APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| 8) BUILDING PROVISO/ DEFERRED SUBMITTALS: FBC 107.3.4.1 |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 107.2.1.2 FOR |
| ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE. |
| FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| |
| 10) BUILDING PROVISO/ DEFERRED SUBMITTALS: EFIS |
| SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE |
| SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.3 STRUCTURAL DESIGN. |
| 1408.4 WEATHER RESISTANCE. |
| 1408.4.1 EIFS WITH DRAINAGE. |
| 408.4.1.1 WATER-RESISTIVE BARRIER. |
| 1408.5 INSTALLATION. |
| |
| 11) COMPLIED FOR SHELL BUILDING. |
| |
| 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |