Plan Review Notes For Permit 17060769 |
Permit Number |
17060769 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-07 12:46:07 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17060769 | | 7/7/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: THE NUMBER OF PEOPLE FOR THE OCCUPANCIES | | LISTED IN THE O/A SCHEDULE ARE NOT IN COMPLIANCE WITH | | EITHER TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3 | | FBC-14 MECHANICAL. OCCUPANT DENSITY FOR RETAIL IS 15 | | PERSONS PER 1000 SQ. FT. WHICH RESULTS IN 32 PEOPLE FOR | | RTU-1, AND 19 PEOPLE FOR RTU-2-8. CONCERNING THE | | RESTAURANT OCCUPANCY (RTU- 9A, 9B, 9C) PLEASE PROVIDE A | | BREAKDOWN CALCULATION THAT DINING AND OTHER AREAS FROM | | THE KITCHEN AREA. PLEASE NOTE THAT THE OCCUPANT DENSITY | | FOR DINING IS 70 PER 1000 SQ. FT. PLEASE REVISE THE | | SCHEDULE ACCORDINGLING. | | | | 2) PLEASE ADJUST THE AC COOLING AND HEATING | | CALCULATIONS TO INCLUDE THE ACCURATE NUMBER OF | | OCCUPANTS AND ALSO THE APPLIANCE LOADS FOR EACH | | OCCUPANCY. | | | | 3) SHEETS M2.1 & S4.3: PLEASE CHOOSE ONE OF THE TWO RTU | | AND CURB INSTALLATION DETAILS WILL BE USED, AND MATCH | | THE OTHER DETAIL TO IT. THERE ARE DIFFERENCES BETWEEN | | THE TYPES AND NUMBER QUANTITIES OF FASTENERS AND ANCHOR | | BOLTS. CORRECT THE WIND SPEED SHOWN ON M2.1 TO 170 MPH. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|