Plan Review Notes
Plan Review Notes For Permit 17060769
Permit Number 17060769
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-07 12:46:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060769
 7/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE NUMBER OF PEOPLE FOR THE OCCUPANCIES
 LISTED IN THE O/A SCHEDULE ARE NOT IN COMPLIANCE WITH
 EITHER TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3
 FBC-14 MECHANICAL. OCCUPANT DENSITY FOR RETAIL IS 15
 PERSONS PER 1000 SQ. FT. WHICH RESULTS IN 32 PEOPLE FOR
 RTU-1, AND 19 PEOPLE FOR RTU-2-8. CONCERNING THE
 RESTAURANT OCCUPANCY (RTU- 9A, 9B, 9C) PLEASE PROVIDE A
 BREAKDOWN CALCULATION THAT DINING AND OTHER AREAS FROM
 THE KITCHEN AREA. PLEASE NOTE THAT THE OCCUPANT DENSITY
 FOR DINING IS 70 PER 1000 SQ. FT. PLEASE REVISE THE
 SCHEDULE ACCORDINGLING.
  
 2) PLEASE ADJUST THE AC COOLING AND HEATING
 CALCULATIONS TO INCLUDE THE ACCURATE NUMBER OF
 OCCUPANTS AND ALSO THE APPLIANCE LOADS FOR EACH
 OCCUPANCY.
  
 3) SHEETS M2.1 & S4.3: PLEASE CHOOSE ONE OF THE TWO RTU
 AND CURB INSTALLATION DETAILS WILL BE USED, AND MATCH
 THE OTHER DETAIL TO IT. THERE ARE DIFFERENCES BETWEEN
 THE TYPES AND NUMBER QUANTITIES OF FASTENERS AND ANCHOR
 BOLTS. CORRECT THE WIND SPEED SHOWN ON M2.1 TO 170 MPH.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER