2017-06-28 12:14:561560 PALM BEACH LAKES BOULEVARD
 PERMIT #17060769
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****SHELL ONLY***** SEPARATE PERMITS AND SUBPERMITS
 WILL BE NEEDED FOR TENANT FITOUT WORK. NO CERTIFICATE
 OF OCCUPANCY WILL BE GRANTED FOR THE SHELL-ONLY WORK.
  
 DESIGN SHALL CONFORM TO THE 5TH EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 NO SITE OR CIVIL PLANS SUBMITTED SHOWING FIRE HYDRANTS
 FOR FIRE DEPARTMENT ACCESS ROADS/LANES.
  
 PLANS DO NOT INDICATE ANY PORTABLE FIRE EXTINGUISHERS,
 EMERGENCY LIGHTING, ILLUMINATED EXIT SIGNS, TACTILE
 SIGNAGE.
  
 PER NFPA 101 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING "FIRE BARRIER-PROTECT ALL OPENINGS." CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 FIRE PROTECTION BACKFLOW PREVENTER IS LOCATED CLOSER
 THAN 40 FEET FROM THE BUILDING.
 PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE
 FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE
 ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO
 THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 PROVIDE A DRAWING NOTE INDICATING: AN APPROVED WRITTEN
 EMERGENCY PLAN FOR THE EMERGENCY EGRESS OF OCCUPANTS IS
 REQUIRED PRIOR TO OCCUPANCY. ALL EMPLOYEES SHALL BE
 INSTRUCTED AND PERIODICALLY DRILLED WITH RESPECT TO
 THEIR DUTIES UNDER THE PLAN. EMPLOYEES SHALL BE
 PERIODICALLY TRAINED OR INSTRUCTED IN THE USE OF
 PORTABLE FIRE EXTINGUISHERS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  