2017-07-13 10:07:46 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. |
| 2. NOTE 8 ON RISER DIAGRAM STATES THE EQUIPMENT |
| GROUNDING CONDUCTOR (EGC) IS SIZED AT 1/0 COPPER, WHICH |
| IS NOT PER CODE FOR A 1200 AMP SYSTEM. PROVIDE |
| CORRECTION. NEC 250.122 |
| 3. PROVIDE ACTUAL FAULT CURRENT FROM FPL. AN ESTIMATED |
| VALUE IS NOT ACCEPTABLE. NEC 110.10 |
| 4. SHEET EP1.2, PLEASE IDENTIFY WHICH LIGHT FIXTURE |
| MODEL WILL BE USED. FBC 107.2.1 |
| 5. INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY |
| CODE. A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE |
| INDICATION OF SUBMITTAL OF COMPLETION DOCUMENTS PER FBC |
| C405.7.4 FBC C405.7.3 |
| 6. LOAD CALCULATIONS PROVIDED IS INCOMPLETE. PROVIDE |
| ACCURATE LOAD CALCULATIONS TO JUSTIFY SERVICE SIZE. NEC |
| 215.2, 215.5, 220; FBC 107.2.1 |
| 7. WHY IS WIRING SHOWN TO THE RTU'S IN UNIT 9, BUT NOT |
| IN ANY OTHER UNIT? WHY IS THERE NO WIRING SHOWN TO |
| EMERGENCY AND EXIT LIGHTS REQUIRED? PROVIDE |
| CLARIFICATION. FBC 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |