Plan Review Notes
Plan Review Notes For Permit 17060769
Permit Number 17060769
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-13 10:07:46CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 2. NOTE 8 ON RISER DIAGRAM STATES THE EQUIPMENT
 GROUNDING CONDUCTOR (EGC) IS SIZED AT 1/0 COPPER, WHICH
 IS NOT PER CODE FOR A 1200 AMP SYSTEM. PROVIDE
 CORRECTION. NEC 250.122
 3. PROVIDE ACTUAL FAULT CURRENT FROM FPL. AN ESTIMATED
 VALUE IS NOT ACCEPTABLE. NEC 110.10
 4. SHEET EP1.2, PLEASE IDENTIFY WHICH LIGHT FIXTURE
 MODEL WILL BE USED. FBC 107.2.1
 5. INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY
 CODE. A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE
 INDICATION OF SUBMITTAL OF COMPLETION DOCUMENTS PER FBC
 C405.7.4 FBC C405.7.3
 6. LOAD CALCULATIONS PROVIDED IS INCOMPLETE. PROVIDE
 ACCURATE LOAD CALCULATIONS TO JUSTIFY SERVICE SIZE. NEC
 215.2, 215.5, 220; FBC 107.2.1
 7. WHY IS WIRING SHOWN TO THE RTU'S IN UNIT 9, BUT NOT
 IN ANY OTHER UNIT? WHY IS THERE NO WIRING SHOWN TO
 EMERGENCY AND EXIT LIGHTS REQUIRED? PROVIDE
 CLARIFICATION. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  