2017-07-20 14:08:401ST REVIEW: FBC 2014 5TH EDITION
  
 PROVISO;
 PROVIDE CODE COMPLIANT PLUMBING RISER DIAGRAM BEFORE
 FIRST ROUGH INSPECTION.
  
 COMMENTS
 1. THE SHOWER SHALL CONNECT TO WET VENT SEPARATELY FROM
 WC PER FBC RES P3108.1
 2. THE TUB IS MISSING FROM THE RISER DIAGRAM AND SHALL
 CONNECT TO WET VENT SEPARATELY FROM WC PER FBC RES
 P3108.1
 3. PROVIDE SCOPE OF PLUMBING WORK. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  