Plan Review Notes For Permit 17060767 |
Permit Number |
17060767 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-20 14:08:40 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PROVISO; | | PROVIDE CODE COMPLIANT PLUMBING RISER DIAGRAM BEFORE | | FIRST ROUGH INSPECTION. | | | | COMMENTS | | 1. THE SHOWER SHALL CONNECT TO WET VENT SEPARATELY FROM | | WC PER FBC RES P3108.1 | | 2. THE TUB IS MISSING FROM THE RISER DIAGRAM AND SHALL | | CONNECT TO WET VENT SEPARATELY FROM WC PER FBC RES | | P3108.1 | | 3. PROVIDE SCOPE OF PLUMBING WORK. PER WPB AMEND TO FBC | | 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|