2017-07-13 12:09:20 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| SAMANTHA HILL |
| [email protected] |
| 561-805-6724 |
| |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT, OR |
| PLEASE CALL ME TO DISCUSS OPTIONS |
| |
| FROM PREVIOUS LIST: |
| PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| SUBMITTALS: |
| |
| 1. OK. |
| 2. OK |
| 3. STATED VALUE OF WORK. - VALUE TOO LOW; VALUE SHOULD |
| INCLUDE THE VALUE OF LABOR, MATERIALS, OVERHEAD, |
| PROFIT, EVEN IF PROVIDED BY OTHERS |
| 4. DESCRIPTION OF EXISTING SITE: |
| 5. A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| CONCRETE/SUSPENDED GYPSUM) - NOT ADDRESSED; OUR RECORDS |
| SHOW 7" SLAB |
| 6. PROPOSED UNDERLAYMENT. - QUIETWALK UNDERLAYMENT TEST |
| REPORTS SUBMITTED |
| 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT PER ASTM |
| E-84, E-90 & E-492. - TEST REPORTS FOR STC/IIC ARE FOR |
| AN 8" SLAB, THIS FLOOR HAS A 7" SLAB, PLEASE ADDRESS |
| 8. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| |
| FBC 603.1 FLAME SPREAD - ASTM E-84 - NOT ADDRESSED |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |