Plan Review Notes
Plan Review Notes For Permit 17060730
Permit Number 17060730
Review Stop B
Sequence Number 2
Notes
Date Text
2017-07-13 12:09:20BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 SAMANTHA HILL
 [email protected]
 561-805-6724
  
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT, OR
 PLEASE CALL ME TO DISCUSS OPTIONS
  
 FROM PREVIOUS LIST:
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. OK.
 2. OK
 3. STATED VALUE OF WORK. - VALUE TOO LOW; VALUE SHOULD
 INCLUDE THE VALUE OF LABOR, MATERIALS, OVERHEAD,
 PROFIT, EVEN IF PROVIDED BY OTHERS
 4. DESCRIPTION OF EXISTING SITE:
 5. A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM) - NOT ADDRESSED; OUR RECORDS
 SHOW 7" SLAB
 6. PROPOSED UNDERLAYMENT. - QUIETWALK UNDERLAYMENT TEST
 REPORTS SUBMITTED
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT PER ASTM
 E-84, E-90 & E-492. - TEST REPORTS FOR STC/IIC ARE FOR
 AN 8" SLAB, THIS FLOOR HAS A 7" SLAB, PLEASE ADDRESS
 8. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E-84 - NOT ADDRESSED
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  