Plan Review Notes
Plan Review Notes For Permit 17060725
Permit Number 17060725
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-23 18:08:36PLAN
 REVIEW COMMENTS
  
 2ND REVIEW FBC 5TH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE ACTUAL TEST REPORTS FROM AN
 APPROVED TESTING AGENCY (NOT THE TECHNICAL DATA FROM
 THE MANUFACTURER) FOR THE VINYL PLANK FLOORING AND THE
 RUBBER FOAM PAD SOUND INSULATION. THE TEST HAVE TO
 REFLECT THE CONSTRUCTION CONDITIONS. IN THIS CASE MOST
 OF THE AREA THAT WILL BE COVERED HAS A 7" EXPOSED
 CONCRETE SLAB BELOW IT. FBC 107.2.1
  
 2) TILE, WOOD AND OTHER TYPES OF HARD FLOORING ARE
 REQUIRED TO COMPLY WITH SOUND TRANSMISSION LIMITATIONS.
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
 FBC 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 3) SUBMIT TWO COPIES OF THE FLOORINGS SOUND INSULATION
 PRODUCT'S TEST REPORT THAT SHOWS COMPLIANCE WITH FBC
 603 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION
 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL
 BE PERMITTED IN BUILDINGS OF TYPE I OR II CONSTRUCTION
 IN THE FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
 4) SUBMIT TWO COPIES OF THE FLOORINGS SOUND INSULATION
 PRODUCT'S TEST REPORT THAT SHOWS COMPLIANCE WITH FBC
 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE INDICATED IN THIS SECTION, FOAM PLASTIC
 INSULATION AND FOAM PLASTIC CORES OF MANUFACTURED
 ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE
 THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN
 450 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR
 USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. LOOSE
 FILL-TYPE FOAM PLASTIC INSULATION SHALL BE TESTED AS
 BOARD STOCK FOR THE FLAME SPREAD AND SMOKE-DEVELOPED
 INDEXES.
  
  
  