2018-01-03 15:53:55 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENT NOT |
| ADDRESSED SATISFACTORILY HAVE FURTHER COMMENTS IN |
| PARENTHESES. COMMENTS CORRECTED ARE NOTED. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B |
| TO CWP IS INCORRECT IN SIZE AND LOCATION. GEC MUST BE |
| SIZED PER NEC 250.66. ADDITIONALLY, ALL GROUNDING |
| ELECTRODES PRESENT MUST BE BONDED TOGETHER, NOT JUST |
| THE CWP. NEC 250.50; FBC RE3608.1 (GROUNDING ELECTRODE |
| SYSTEM IS ESTABLISHED AT THE MAIN SERVICE, WHICH IS |
| LOCATED ON THE SIDE OF THE GARAGE. THE ONLY OTHER |
| LOCATION FOR A GROUNDING ELECTRODE WOULD BE AT A |
| SEPARATE STRUCTURE. PROVIDE CORRECTION.) |
| 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE |
| FOR PANEL C. NEC 215.5 (NOT PROVIDED. ADDITIONALLY, NO |
| LOAD FOR PANEL C IS SHOWN IN THE PANEL SCHEDULE FOR |
| PANEL B. PROVIDE CORRECTION.) |
| 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 (NOT SHOWN ON PLAN.) |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. CORRECTED. |
| 9. CORRECTED. |
| 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A |
| SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS |
| REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY, |
| A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING |
| AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE |
| CORRECTION. FBC R314, R315 (NOT PROVIDED, A NOTE IS NOT |
| SUFFICIENT.) |
| 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS |
| LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC |
| 410.16(B), FBC RE4003.12 (STATING THAT LED LIGHTS WILL |
| BE USED IS NOT SUFFICIENT AS MANY LED LIGHTS HAVE OPEN |
| BULBS. PROVIDE CORRECTION AS PREVIOUSLY REQUESTED.) |
| 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH |
| OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES |
| OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS. |
| PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12 |
| (STATING THAT LED LIGHTS WILL BE USED IS NOT SUFFICIENT |
| AS MANY LED LIGHTS HAVE OPEN BULBS. PROVIDE CORRECTION |
| AS PREVIOUSLY REQUESTED.) |
| 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB. |
| LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A), |
| FBC RE4003.11 (CORRECTION NOT PROVIDED. LIGHTING ABOVE |
| TUB MUST BE VAPOR ROOF. PROVIDE AS REQUESTED.) |
| 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY |
| AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS. |
| PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11 |
| (NOT PROVIDED.) |
| |
| NEW COMMENTS: |
| 15. NOTE UNDER RECESS LIGHTS STATES THAT 50% OF |
| LIGHTING SHALL BE HIGH EFFICIENCY. PROVIDE COMPLIANCE: |
| "A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1 |
| 16. PLEASE BE ADVISED THAT SOME OF THE COMMENTS HAVE |
| NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD |
| REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN |
| REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |