2017-07-05 12:02:501ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1.THE ENERGY CALCULATIONS SHOW A PROPANE TANKLESS
 HEATER OR IS IT A NATURAL GAS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE SOIL STACK FOR SECOND FLOOR IN MAIN HOUSE SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM
 GROUP. PER FBC RES P3108.1
  
 3. A CLEAN OUT IS REQUIRED AT THE BASE OF EVERY SOIL
 STACK. PER FBC RES P3005.2.6
  
 4. THE LAUNDRY SINK AND WASHING MACHINE IN MAIN HOUSE
 SHALL BE SHOWN ON THE RISER CONNECTED TO SECOND FLOOR
 PIPING. PER FBC RES P3108.1
  
 5. THE KITCHEN SINK IN THE OUTDOOR KITCHEN SHALL
 CONNECT DOWN STREAM OF THE BATHROOM. PER FBC RES
 P3108.1
  
 6. THE LAV IN THE DOWN STAIRS BATHROOM IN DETACHED
 GARAGE IS NIT VENTED. PER FBC RES P3101.2.1
  
 7. THE WASHING MACHINE UPSTAIRS IN THE DETACHED GARAGE
 IS NOT SHOWN ON THE RISER DIAGRAM PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 8. ISLAND SINK UPSTAIRS IN DETACHED GARAGE SHALL
 CONNECT DOWN STREAM OF THE BATHROOM GROUP. PER FBC RES
 P3108.1
  
 9. PROVIDE ACCESS TO THE SHUT OFF VALVES FOR STACKABLE
 WASHING MACHINES . PER FBC RES P2903.9.3
  
 10. PLEASE SHOW LOCATION OF WATER HEATERS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  