2017-06-30 09:15:44 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE GROUNDING ELECTRODE SYSTEM FOR MAIN HOUSE AS |
| REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A |
| FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3 |
| 2. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL A |
| TO CWP IS INCORRECT IN SIZE AND LOCATION. ALL GROUNDING |
| ELECTRODE CONDUCTORS MUST ATTACH TO THE GROUNDED |
| SERVICE CONDUCTOR ON THE SUPPLY SIDE OF THE SERVICE AND |
| SHALL BE SIZED PER NEC 250.66. NEC 250.64(D)(3); FBC |
| RE3607.1 |
| 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B |
| TO CWP IS INCORRECT IN SIZE. GEC MUST BE SIZED PER NEC |
| 250.66. ADDITIONALLY, ALL GROUNDING ELECTRODES PRESENT |
| MUST BE BONDED TOGETHER, NOT JUST THE CWP. SEE COMMENT |
| #1 ALSO. NEC 250.50; FBC RE3608.1 |
| 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE |
| FOR PANEL C. NEC 215.5 |
| 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 6. PANEL B, CIRCUITS 2,4 AND 6,8 AND 10,12 SHOW A #6 |
| ROMEX WIRE ON A 60 AMP BREAKER. #6 WIRE IS NOT RATED |
| FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC |
| RE3705.4.4 |
| 7. PANEL C, CIRCUIT 2,4 SHOW A #6 ROMEX WIRE ON A 60 |
| AMP BREAKER. #6 WIRE IS NOT RATED FOR 60 AMPS. PROVIDE |
| CORRECTION. NEC 334.80; FBC RE3705.4.4 |
| 8. NOTE ON RISER DIAGRAM STATES "PER 2008 NEC". CORRECT |
| TO CURRENT CODE, 2011 NEC. FBC PREFACE |
| 9. PROVIDE 20 AMP CIRCUIT FOR BATH GFCI OUTLETS. A |
| MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11(C)(3) |
| , FBC RE3703.4 |
| 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A |
| SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS |
| REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY, |
| A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING |
| AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE |
| CORRECTION. FBC R314, R315 |
| 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS |
| LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC |
| 410.16(B), FBC RE4003.12 |
| 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH |
| OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES |
| OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS. |
| PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12 |
| 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB. |
| LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A), |
| FBC RE4003.11 |
| 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY |
| AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS. |
| PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |