2017-06-30 09:15:44CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE GROUNDING ELECTRODE SYSTEM FOR MAIN HOUSE AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 2. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL A
 TO CWP IS INCORRECT IN SIZE AND LOCATION. ALL GROUNDING
 ELECTRODE CONDUCTORS MUST ATTACH TO THE GROUNDED
 SERVICE CONDUCTOR ON THE SUPPLY SIDE OF THE SERVICE AND
 SHALL BE SIZED PER NEC 250.66. NEC 250.64(D)(3); FBC
 RE3607.1
 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B
 TO CWP IS INCORRECT IN SIZE. GEC MUST BE SIZED PER NEC
 250.66. ADDITIONALLY, ALL GROUNDING ELECTRODES PRESENT
 MUST BE BONDED TOGETHER, NOT JUST THE CWP. SEE COMMENT
 #1 ALSO. NEC 250.50; FBC RE3608.1
 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE
 FOR PANEL C. NEC 215.5
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 6. PANEL B, CIRCUITS 2,4 AND 6,8 AND 10,12 SHOW A #6
 ROMEX WIRE ON A 60 AMP BREAKER. #6 WIRE IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 7. PANEL C, CIRCUIT 2,4 SHOW A #6 ROMEX WIRE ON A 60
 AMP BREAKER. #6 WIRE IS NOT RATED FOR 60 AMPS. PROVIDE
 CORRECTION. NEC 334.80; FBC RE3705.4.4
 8. NOTE ON RISER DIAGRAM STATES "PER 2008 NEC". CORRECT
 TO CURRENT CODE, 2011 NEC. FBC PREFACE
 9. PROVIDE 20 AMP CIRCUIT FOR BATH GFCI OUTLETS. A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11(C)(3)
 , FBC RE3703.4
 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A
 SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS
 REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY,
 A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING
 AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE
 CORRECTION. FBC R314, R315
 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS
 LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH
 OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES
 OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS.
 PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12
 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A),
 FBC RE4003.11
 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY
 AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS.
 PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER