Plan Review Notes For Permit 17060562 |
Permit Number |
17060562 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-08-09 13:16:14 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ONLY ONE COPY OF PLAN WAS SUBMITTED. 2 COPIES ARE | | REQUIRED. FBC 107.1 | | 2. PER CONVERSATION WITH CONTRACTOR, THE PLAN SHOULD | | STATE THAT ALL ELECTRICAL WORK IS EXISTING AND THEY | | SCOPE OF WORK IS TO INSTALL LIGHT FIXTURES ONLY. FBC | | 107.2.1 | | 3. PLAN SHOWS 3 DIFFERENT MODELS, WHICH IS THE LAYOUT | | FOR THIS UNIT? PROVIDE CORRECT LAYOUT AND REMOVE ANY | | SHEETS THAT ARE IRRELEVANT. FBC 107.2.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|