Plan Review Notes
Plan Review Notes For Permit 17060562
Permit Number 17060562
Review Stop E
Sequence Number 2
Notes
Date Text
2017-07-05 14:45:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL 2ND REVIEW COMMENTS:
  
 1. PREVIOUS COMMENT NOT ADDRESSED: "NO ELECTRICAL PLAN
 PROVIDED FOR REVIEW. PROVIDE PLAN SHOWING ALL
 ELECTRICAL WORK". WITH EACH APPLICATION, THERE ARE
 SEVERAL DIFFERENT FLOOR LAYOUTS. REMOVE ANY ITEMS NOT
 RELATED TO THE UNIT IN QUESTION AND PROVIDE ELECTRICAL
 PLAN SHOWING WHICH FIXTURES WILL BE
 REMOVED/REPLACED/INSTALLED. ELECTRICAL PLAN IS REQUIRED
 TO BE SIGNED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC
 107.3.5
 2. PREVIOUS COMMENT NOT ADDRESSED: "PROVIDE COPY OF
 CONTRACT SHOWING TOTAL COST OF JOB, TO INCLUDE LABOR
 AND MATERIALS". PROVIDING AN UNSIGNED CONTRACT WITH A
 PER FIXTURE PRICE IS NOT ACCEPTABLE. PROVIDE TOTAL
 VALUE OF JOB FOR EACH UNIT, INCLUDING LABOR AND COST OF
 FIXTURES. PROVIDE SPEC SHEET OF LIGHT FIXTURES. NEC
 110.3; FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  