2017-07-05 14:45:59 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL 2ND REVIEW COMMENTS: |
| |
| 1. PREVIOUS COMMENT NOT ADDRESSED: "NO ELECTRICAL PLAN |
| PROVIDED FOR REVIEW. PROVIDE PLAN SHOWING ALL |
| ELECTRICAL WORK". WITH EACH APPLICATION, THERE ARE |
| SEVERAL DIFFERENT FLOOR LAYOUTS. REMOVE ANY ITEMS NOT |
| RELATED TO THE UNIT IN QUESTION AND PROVIDE ELECTRICAL |
| PLAN SHOWING WHICH FIXTURES WILL BE |
| REMOVED/REPLACED/INSTALLED. ELECTRICAL PLAN IS REQUIRED |
| TO BE SIGNED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL |
| CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC |
| 107.3.5 |
| 2. PREVIOUS COMMENT NOT ADDRESSED: "PROVIDE COPY OF |
| CONTRACT SHOWING TOTAL COST OF JOB, TO INCLUDE LABOR |
| AND MATERIALS". PROVIDING AN UNSIGNED CONTRACT WITH A |
| PER FIXTURE PRICE IS NOT ACCEPTABLE. PROVIDE TOTAL |
| VALUE OF JOB FOR EACH UNIT, INCLUDING LABOR AND COST OF |
| FIXTURES. PROVIDE SPEC SHEET OF LIGHT FIXTURES. NEC |
| 110.3; FBC 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |