2017-06-29 11:16:21 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060556 (MASTER) |
| TRAVELING TOGETHER 17060559, 17060562, 17060565, |
| 17060568, 17060571, |
| 17060574, 17060578, 17060581, 17060584, 17060587, |
| 17060590, 17060593, 17060596, 17060599, 17060602, |
| 17060605, 17060608, 17060611, 17060614 |
| |
| ADD: 410 EVERNIA ST. SUITE NUMBER 802 |
| CONT: URBAN TEAM CONSTRUCTION |
| TEL: 305-710-3886 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JUNE 29/2017 |
| ACTION: DENIED |
| |
| 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| |
| |
| |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| |
| 1) 2ND REQUEST THE VALUES STATED ARE EXTREMELY LOW FOR |
| THE VALUE STATED AND THE SCOPE OF WORK. 108.3 IS FOR |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| AND PROFIT. |
| I?VE SPOKEN WITH THE CHIEF PLUMBING INSPECTOR AND FOR |
| THE REPLACEMENT OF T FIXTURES, REMOVAL, DISPOSAL, LABOR |
| TO BRING THE NEW FIXTURES TO THE TENANT UNIT, UNPACK |
| SET AND INSTALL NEW VALVES, SPOUT, HANDLES, SHOWER |
| HEADS, PLUS LABOR AND OVERHEAD A MINIMUM OF $2,500.00 |
| PER UNIT WOULD BE A MINIMUM VALUE WE WOULD ACCEPT WE |
| BELIEVE THE ACTUAL VALUE IS $3,500.00 PER UNIT. |
| IN REGARDS TO THE VALUE STATED FOR THE REMOVAL & |
| INSTALLATION OF LIGHT FIXTURES, THE $25.00 DOLLARS |
| STATED IS THE AVERAGE WAGE FOR AN ELECTRICIAN, NOT THE |
| VALUE THE CONTRACTOR CHARGES, THE RATE CHARGED CAN BE |
| AS HIGH AS $90.00 DEPENDING ON THE COMPLEXITY AND TYPE |
| OF JOB. WE WILL USE $75.00 FOR THE AVERAGE RATE FOR AN |
| ELECTRICIAN, PLEASE PROVIDE THE CUT SHEETS FOR |
| FIXTURES, COST OF THE FIXTURE AND BULB. . FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING, |
| MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK |
| (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT. |
| |
| 1ST ROUND OF COMMENTS. FOR THE SCOPE OF WORK THE VALUE |
| OF THE PROJECT IS LOW. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) COMPLIED. PLEASE PROVIDE A FLOOR PLAN OF THE FLOOR |
| FINISHES TO BE REPLACE AND WHAT FINISH MATERIALS. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) 2ND REQUEST. SAME COMMENT AS THE 1ST REVIEW. THE |
| QUALIFIER OF THE COMPANY HAS TO TAKE OWNERSHIP OF THE |
| PLANS SUBMITTED UNLESS THE PLANS ARE DESIGNED BY EITHER |
| AN ARCHITECT UNDER F. S 481 OR AN ENGINEER UNDER F. S. |
| 471. |
| 1ST ROUND OF COMMENTS. THE AUTHOR (QUALIFIER OF |
| COMPANY) OF THE FLOOR PLAN IS TO PRINT THEIR NAME, SIGN |
| THEIR NAME AND PRINT THEIR LICENSE NUMBER OF THE PLANS |
| THEY DREW. 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE |
| CHARGE. |
| 4) 2ND REQUEST. THE SUBMITTED SHAW SUNDRIES GROUND |
| WORKS ACOUSTICAL UNDERLAYMENT STYLE 074VS IS A SALES |
| BROCHURE LISTING TESTING, NOT THE ACTUAL TEST REPORTS. |
| SEE 1ST ROUND OF COMMENTS. |
| |
| 1ST ROUND OF COMMENTS. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| INSULATION (FBC-B 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 4A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 4C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |