Plan Review Notes
Plan Review Notes For Permit 17060562
Permit Number 17060562
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-29 11:16:212014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060556 (MASTER)
 TRAVELING TOGETHER 17060559, 17060562, 17060565,
 17060568, 17060571,
 17060574, 17060578, 17060581, 17060584, 17060587,
 17060590, 17060593, 17060596, 17060599, 17060602,
 17060605, 17060608, 17060611, 17060614
  
 ADD: 410 EVERNIA ST. SUITE NUMBER 802
 CONT: URBAN TEAM CONSTRUCTION
 TEL: 305-710-3886
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 29/2017
 ACTION: DENIED
  
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 2ND REQUEST THE VALUES STATED ARE EXTREMELY LOW FOR
 THE VALUE STATED AND THE SCOPE OF WORK. 108.3 IS FOR
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT.
 I?VE SPOKEN WITH THE CHIEF PLUMBING INSPECTOR AND FOR
 THE REPLACEMENT OF T FIXTURES, REMOVAL, DISPOSAL, LABOR
 TO BRING THE NEW FIXTURES TO THE TENANT UNIT, UNPACK
 SET AND INSTALL NEW VALVES, SPOUT, HANDLES, SHOWER
 HEADS, PLUS LABOR AND OVERHEAD A MINIMUM OF $2,500.00
 PER UNIT WOULD BE A MINIMUM VALUE WE WOULD ACCEPT WE
 BELIEVE THE ACTUAL VALUE IS $3,500.00 PER UNIT.
 IN REGARDS TO THE VALUE STATED FOR THE REMOVAL &
 INSTALLATION OF LIGHT FIXTURES, THE $25.00 DOLLARS
 STATED IS THE AVERAGE WAGE FOR AN ELECTRICIAN, NOT THE
 VALUE THE CONTRACTOR CHARGES, THE RATE CHARGED CAN BE
 AS HIGH AS $90.00 DEPENDING ON THE COMPLEXITY AND TYPE
 OF JOB. WE WILL USE $75.00 FOR THE AVERAGE RATE FOR AN
 ELECTRICIAN, PLEASE PROVIDE THE CUT SHEETS FOR
 FIXTURES, COST OF THE FIXTURE AND BULB. . FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING,
 MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT.
  
 1ST ROUND OF COMMENTS. FOR THE SCOPE OF WORK THE VALUE
 OF THE PROJECT IS LOW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) COMPLIED. PLEASE PROVIDE A FLOOR PLAN OF THE FLOOR
 FINISHES TO BE REPLACE AND WHAT FINISH MATERIALS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) 2ND REQUEST. SAME COMMENT AS THE 1ST REVIEW. THE
 QUALIFIER OF THE COMPANY HAS TO TAKE OWNERSHIP OF THE
 PLANS SUBMITTED UNLESS THE PLANS ARE DESIGNED BY EITHER
 AN ARCHITECT UNDER F. S 481 OR AN ENGINEER UNDER F. S.
 471.
 1ST ROUND OF COMMENTS. THE AUTHOR (QUALIFIER OF
 COMPANY) OF THE FLOOR PLAN IS TO PRINT THEIR NAME, SIGN
 THEIR NAME AND PRINT THEIR LICENSE NUMBER OF THE PLANS
 THEY DREW. 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE.
 4) 2ND REQUEST. THE SUBMITTED SHAW SUNDRIES GROUND
 WORKS ACOUSTICAL UNDERLAYMENT STYLE 074VS IS A SALES
 BROCHURE LISTING TESTING, NOT THE ACTUAL TEST REPORTS.
 SEE 1ST ROUND OF COMMENTS.
  
 1ST ROUND OF COMMENTS. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER