2018-02-20 17:02:353RD REVIEW FBC-2014 MECHANICAL
 REVISION #17060532
 MASTER #16041147
 12/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1 AND #3 FROM THE 1ST AND 2ND REVIEWS WERE
 NOT ADDRESSED AND STILL EXIST. I HAVE REPRINTED THE
 COMMENTS BELOW- PLEASE COMPLY.
  
 1) THE AC CONTRACTOR WHO PREPARED THE REVISED
 MECHANICAL PLAN (KAREN OLIVER) SHALL SUBMIT A
 SUB-PERMIT APPLICATION AS REQUIRED BY SECTION 105.3.1.2
 ITEM #3 WPB AMENDMENTS TO THE FBC-10 BUILDING. IF SHE
 IS NOT THE INSTALLING MECHANICAL CONTRACTOR ON THE
 PROJECT THAN SHE CANNOT BE THE MECHANICAL DESIGNER.
  
 3) REFER TO SECTION 602.1: THE NEW AC CLOSETS ARE
 PLENUM ENCLOSURES AND MUST BE CONTRUCTED IN ACCORDANCE
 WITH SECTION 602.2. PLEASE NOTE NON-COMBUSTIBLE CLOSET
 DOORS ARE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  