2017-12-28 12:13:032ND REVIEW FBC-2014 MECHANICAL
 REVISION #17060532
 MASTER #16041147
 12/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 AND #3 FROM THE 1ST REVIEW WERE NOT
 ADDRESSED AND STILL EXIST. I HAVE REPRINTED THOSE
 COMMENTS BELOW- PLEASE COMPLY.
  
 ONLY ONE SET OF ENERGY CALCULATIONS AND AC CALCULATIONS
 WERE RESUBMITTED. PLEASE PROVIDE THE SECOND COPIES.
  
 1) THE AC CONTRACTOR WHO PREPARED THE REVISED
 MECHANICAL PLAN SHALL SUBMIT A SUB-PERMIT APPLICATION
 AS REQUIRED BY SECTION 105.3.1.2 ITEM #3 WPB AMENDMENTS
 TO THE FBC-10 BUILDING.
  
 3) REFER TO SECTION 602.1: THE NEW AC CLOSETS ARE
 PLENUM ENCLOSURES AND MUST BE CONTRUCTED IN ACCORDANCE
 WITH SECTION 602.2. PLEASE NOTE NON-COMBUSTIBLE CLOSET
 DOORS ARE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  