Plan Review Notes
Plan Review Notes For Permit 17060532
Permit Number 17060532
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-15 11:37:221ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060532
 6/15/17
  
 RESULTS: DENIED.
  
 1) THE AC CONTRACTOR WHO PREPARED THE REVISED
 MECHANICAL PLAN SHALL SUBMIT A SUB-PERMIT APPLICATION
 AS REQUIRED BY SECTION 105.3.1.2 ITEM #3 WPB AMENDMENTS
 TO THE FBC-10 BUILDING.
  
 2) THE ENGINEER OF RECORD MAURICE EVAN LORD PE WHO DID
 THE ORIGINAL MECHANICAL DESIGN ON SHEET E-1 MUST
 PROVIDE REVISED ELECTRICAL PLANS TO ACCOMODATE THE NEW
 AC SYSTEM. BECAUSE LORD IS STILL THE MECHANICAL
 DESIGNER OF RECORD, HE MUST REVIEW AND APPROVE THE NEW
 AC DRAWINGS.
  
 3) REFER TO SECTION 602.1: THE NEW AC CLOSETS ARE
 PLENUM ENCLOSURES AND MUST BE CONTRUCTED IN ACCORDANCE
 WITH SECTION 602.2. PLEASE NOTE NON-COMBUSTIBLE CLOSET
 DOORS ARE REQUIRED.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CONDENSATE PUMPS.
  
 5) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE
 CONDENSER TIE DOWN CLIPS AND LIST THE NOA NUMBER BY THE
 CONDENSER DETAIL ON SHEET M.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  