Plan Review Notes For Permit 17060531 |
Permit Number |
17060531 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-18 17:48:52 | 1- ROOFING MATERIAL IS NOT CLEAR. MATERIALS AND COLOR | | INFORMATION ON SHEET SP-1 AND WEST ELEVATION ON SHEET | | A-4 CALL FOR SHINGLES TO MATCH EXISTING SHINGLES. BUT, | | PRODUCT APPROVAL FL7804-R9 SUBMITTED IS FOR CONCRETE | | ROOF TILE. PRODUCT APPROVAL AND SPECIFICATIONS NEED TO | | MATCH. SEC. 107.2.1 CITY AMENDMENTS. NOTE: IF USING | | CONCRETE TILE, THEN SPECIFY IF EXISTING HOUSE IS GOING | | TO RECEIVE CONCRETE TILE ALSO. AND, PROVIDE ENGINEERING | | ANALYSIS SHOWING THAT THE EXISTING STRUCTURE IS | | ADEQUATE TO RECEIVE THE ADDITIONAL CONCRETE TILE LOAD. | | SEC. R301.1 FBC-RESIDENTIAL. | | | | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR: | | A) ROOF SHINGLES. NOTE: COORDINATE WITH ITEM ABOVE. | | | | B) ROOF UNDERLAYMENT. FLORIDA PRODUCT APPROVAL | | FL5259-R25 SUBMITTED WAS REVISED. PROVIDE 2 COPIES OF | | REVISED PRODUCT APPROVAL FL5259-R26 AND CLEARLY MARK | | WHICH SPECIFIC UNDERLAYMENT IS GOING TO BE USED. | | | | C) ROOF TILE ADHESIVE AS HIGHLIGHTED ON ROOF TILE | | PRODUCT APPROVAL SUBMITTED. NOTE: COORDINATE WITH ITEM | | #9 ABOVE. | | |
|