2017-07-18 14:06:43RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ARCHITECT OF RECORD TO COORDINATE A/C PLAN WITH
 EQUIPMENT SIZING CALCULATIONS SUBMITTED. CFM'S DON'T
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ARCHITECT TO SPECIFY ON THE A/C PLAN THE CFM'S FOR
 THE EXISTING LIVING ROOM. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 3- ARCHITECT TO SPECIFY ON PLANS THE EQUIPMENT
 MANUFACTURER AND MODEL #. SEC. 107.3.5.3(10) CITY
 AMENDMENTS. COORDINATE WITH THE EQUIPMENT SIZING
 CALCULATIONS SUBMITTED.
  
 4- ARCHITECT TO CLARIFY WHY THE RETURN AIR DUCTWORK IS
 CONNECTED TO THE DISCONNECT?. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- ARCHITECT TO SPECIFY ON A/C PLAN COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE NEW FAMILY ROOM AS REQUIRED
 BY SEC. M1602.4 FBC-RESIDENTIAL.
  
 6- PERSON PREPARING THE EQUIPMENT SIZING CALCULATIONS
 TO CLARIFY WHY SPECIFYING 10 PEOPLE FOR A 3 BEDROOM
 HOUSE. TYPICALLY A 3 BEDROOM HOUSE DOESN'T HAVE 10
 OCCUPANTS. NUMBER OF OCCUPANTS MAY AFFECT THE SIZING OF
 THE EQUIPMENT. EQUIPMENT SIZING SHALL BE DONE BASED ON
 THE ACTUAL NUMBER OF PEOPLE. PROVIDE JUSTIFICATIONS OF
 WHY 10 PEOPLE. CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 7- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE
 INCOMPLETE. NEED TO PROVIDE COMPLETE INFORMATION FOR
 THE EQUIPMENT. COORDINATE WITH ARCHITECT'S A/C PLAN.
 ALSO, SEE ARCHITECT'S A/C PLAN FOR CORRECT FLOOR LAYOUT
 AND LOCATION OF REGISTERS. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW SET OF
 PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  