Plan Review Notes For Permit 17060512 |
Permit Number |
17060512 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-29 07:53:26 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR | | QUALIFIER. FS 471.003(2)(H); 471.025 | | 2. NOTE FOR TAMPER RESISTANT OUTLET QUOTES NEC 406.11, | | WHICH IS NOT RELATED TO TAMPER RESISTANT REQUIREMENTS. | | PLEASE CORRECT. NEC 406.12 | | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS | | TO COMPLY WITH CODE. NEC 215.5, 408.4; FBC RE3706.2 | | 4. SHOW ON PLAN THE REQUIRED WALL SPACING OUTLETS IN | | LIVING ROOM WHERE WALL IS RECONFIGURED. FBC 107.2.1; | | NEC 210.52 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|