2017-07-18 16:04:43 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SPECIFY THE DIMENSIONS OF THE PROPOSED BATHROOM FROM |
| THE EXTERIOR WALL AT THE TUB TO THE INTERIOR WALL AT |
| THE FAMILY ROOM. FBC 107.2.1 |
| |
| 2) THE WINDOW IN THE PROPOSED BATHROOM WILL HAVE TO |
| COMPLY WITH FBC - R308.4.5 FOR SAFETY GLAZING. R308.4.5 |
| GLAZING IN WALLS, ENCLOSURES OR FENCES CONTAINING OR |
| FACING HOT TUBS, SPAS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, |
| BATHTUBS, SHOWERS AND INDOOR OR OUTDOOR SWIMMING POOLS |
| WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS |
| THAN 60 INCHES (1524 MM) MEASURED VERTICALLY ABOVE ANY |
| STANDING OR WALKING SURFACE SHALL BE CONSIDERED A |
| HAZARDOUS LOCATION. THIS SHALL APPLY TO SINGLE GLAZING |
| AND ALL PANES IN MULTIPLE GLAZING. IF THE EXISTING |
| WINDOW HAS TO BE REPLACED, SUBMIT TWO SETS OF PRODUCT |
| APPROVALS FOR THE NEW WINDOW. FBC 107.3.4.1 |
| |
| 3) WALL SECTION "A" SHOWS A NEW 5 INCH CONCRETE SLAB |
| POURED OVER THE EXISTING SLAB. THE OTHER DRAWINGS |
| SPECIFY A NEW 4 INCH CONCRETE SLAB OVER THE EXISTING |
| ONE. PLEASE CORRECT. FBC 107.2.1 |
| |
| 4) IN ADDITION TO THE EXISTING ATTIC SPACE, THE 2014 |
| FBC ENERGY CONSERVATION CODE REQUIRES THE EXISTING |
| CONCRETE BLOCK EXTERIOR WALLS TO BE INSULATED. SPECIFY |
| THE CBS WALL INSULATION ON THE PLANS. FBC ENERGY |
| SECTION R402.1 |
| |
| 5) SUBMIT THE REQUIRED FORMS AND MATERIALS TO SHOW THAT |
| THE PROPOSED WORK COMPLIES WITH THE FBC ENERGY CODE. |
| SEE FBC ENERGY CONSERVATION CODE SECTION R101.5.1 |