2017-06-21 10:13:36 | E-MAIL RESPONSE FROM MARK CONRAD: |
| HI MR. GOMEZ-THANKS FOR YOUR EMAIL-ATTACHED IS THE |
| QUOTE FROM MY TILE GUY TO PERFORM THE WORK AT 300 |
| AUSTRALIAN UNIT 213-I DID NOT INCLUDE MY 20% |
| PROFIT/OVERHEAD TO PERMIT VALUE-WILL THIS BE SUFFICIENT |
| DOCUMENTATION? AS FOR SOUND MEMBRANE DOCUMENTATION-I |
| BELIEVE WE INADVERTENTLY GAVE THIS TO THE BUILDING |
| MANAGER SO I WILL BE SURE TO FORWARD THIS DOCUMENTATION |
| TO YOU? WILL THIS BE SATISFACTORY TO ALLOW FOR THE |
| RELEASE OF THIS PERMIT? THANKS VERY MUCH-MARK CONRAD. |
| |
| |
| RESPONSE TO MARK CONRAD: |
| 1- REGARDING THE SOUND MEMBRANE DOCUMENTATION, PLEASE |
| MAKE SURE COPIES OF THE TESTS ARE FOR THE ACTUAL |
| ASSEMBLY OF THIS BUILDING. REVIEW THE DOCUMENTATION |
| BEFORE SUBMITTAL. CHECK THE THICKNESS OF THE CONCRETE |
| SLAB AND IF ACOUSTICAL CEILING IS CONSIDERED IN THE |
| TESTS. SEE ITEMS A,B AND C OF ITEM #1 BELOW. |
| |
| 2- REGARDING THE VALUE. IT LOOKS LIKE THE ESTIMATE |
| SUBMITTED IS ONLY FOR INSTALLATION AND OWNER IS |
| SUPPLYING THE MATERIALS. NEED TO INCLUDE THE COST OF |
| ALL MATERIALS IN THE VALUATION. |
| |
| |
| RESIDENTIAL (R2) ALTERATION. BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- SOUND INSULATION MATERIAL SUBMITTED: |
| A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION |
| (2014). |
| |
| B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014). |
| |
| NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| CONSTRUCTION. TECHNICAL DATA SUBMITTED SHOWS THAT THE |
| TESTS WERE CONDUCTED ON 8" CONCRETE SLAB WITH |
| ACOUSTICAL CEILING. THIS ASSEMBLY DOESN'T MATCH THE |
| ASSEMBLY ON THIS BUILDING. THIS BUILDING HAS A 7" |
| CONCRETE SLAB AND THERE IS NO ACOUSTICAL CEILING. THERE |
| ARE TESTS FOR 6" CONCRETE SLABS WITHOUT ACOUSTICAL |
| CEILING. PROVIDE INFORMATION THAT MORE CLOSELY MATCHES |
| THIS BUILDING ASSEMBLY. |
| |
| C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014). |
| |
| NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| CONSTRUCTION. TECHNICAL DATA SUBMITTED SHOWS THAT THE |
| TESTS WERE CONDUCTED ON 8" CONCRETE SLAB WITH |
| ACOUSTICAL CEILING. THIS ASSEMBLY DOESN'T MATCH THE |
| ASSEMBLY ON THIS BUILDING. THIS BUILDING HAS A 7" |
| CONCRETE SLAB AND THERE IS NO ACOUSTICAL CEILING. THERE |
| ARE TESTS FOR 6" CONCRETE SLABS WITHOUT ACOUSTICAL |
| CEILING. PROVIDE INFORMATION THAT MORE CLOSELY MATCHES |
| THIS BUILDING ASSEMBLY. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| 109.3 CITY AMENDMENTS. NOTE: PROVIDE COPY OF SIGNED |
| CONTRACT FOR ALL SCOPE OF WORK TO BE DONE FOR BUILDING |
| OFFICIAL APPROVAL. |
| |