2017-07-17 08:15:20 | MECHANICAL PROVISOS | | 7/17/2017 | | | | 1) MANUFACTURER'S SPECIFICATIONS FOR THE GAS FIREPLACE, | | GAS RANGE AND EXHAUST HOOD SHALL BE ONSITE AT TIME OF | | ROUGH INSPECTION. | | | | 2) RELOCATE THE LOUVERED DOOR FOR AHU-1 TO AVOID RETURN | | AIR BEING TAKEN FROM THE KITCHEN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|