Plan Review Notes
Plan Review Notes For Permit 17060343
Permit Number 17060343
Review Stop P
Sequence Number 2
Notes
Date Text
2017-08-24 10:09:461) SHT. A-412 - FLOOR PLAN DETAIL #1 - SHOW THE
 DISTANCE BETWEEN THE KITCHEN COUNTER AND THE WALL.
 CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS SHALL BE AT
 LEAST 40 INCHES. REFER TO ELEVATION #20 ON A413.
 FHAG REQ.#7 (1) ( B).
 2) SHT. A-412 - FLOOR PLAN DETAIL #1 - SHOW THE
 REQUIRED 30 INCHES BY 48 INCHES CLEAR FLOOR SPACE FOR
 THE KITCHEN SINK AND SHOW THAT THE CLEAR FLOOR SPACE IS
 CENTERED ON THE FIXTURE.FHAG REQ. #7.
 3) A-412 - FLOOR PLAN DETAIL #1 - SHOW THE DIMENSION
 FROM THE CENTERLINE OF THE WATER CLOSETS TO THE
 ADJOINING WALL IN THE BATHROOMS (18 INCHES REQD.) AND
 ALSO SHOW THE DIMENSION FROM THE ADJOINING WALL NEXT TO
 THE WATER CLOSET TO THE EDGE OF THE LAVATORY. A MINIMUM
 OF 33 INCHES IS REQD. SEE FHAG FIGURE #7A.
 4) SHT. A-412 - SHOW ON THE PLAN THAT THE CLEAR FLOOR
 SPACE FOR THE LAVATORIES IS CENTERED ON THE FIXTURE.
 FHAG FIGURE #7C.
  