Plan Review Notes
Plan Review Notes For Permit 17060343
Permit Number 17060343
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-29 06:00:081) SUBMIT A FLOOR PLAN FOR THE "G" UNIT SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES 24 CFR 100.205. SHOW ALL
 REQUIRED CLEAR FLOOR SPACES AT PLUMBING FIXTURES AND
 SHOW THE DIMENSIONS (LXW) OF THE CLEAR FLOOR SPACES.
 2) INDICATE ON THE FLOOR PLAN FOR THE "G" UNIT WHAT
 DESIGN SPECIFICATION ("A" OR "B") FROM THE FHAG IS
 BEING USED FOR THE BATHROOMS IN THE "G" UNIT.
 3) CLEARLY SHOW ON THE FLOOR PLAN FOR THE UNIT WHICH
 BATHROOM(S) IS THE FHAG COMPLIANT BATHROOM(S).WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) PROVIDE A SANITARY AND WATER RISER DIAGRAM FOR THE
 "G" UNIT. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 5) SHT. P104B - THE TEXT IN THE LOWER RIGHT HAND CORNER
 CALLS OUT A "B" FLOOR PLAN BUT THE UNITS ARE ALL SHOWN
 AS "C" UNITS ON THE PLAN. CLARIFY.
 6) SHT.P210A - THE NARRATIVE REFERS TO A HOT WATER
 RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE
 LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SHT. 210B - THE NARRATIVE REFERS TO A HOT WATER
 RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE
 LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW