2017-06-29 06:00:08 | 1) SUBMIT A FLOOR PLAN FOR THE "G" UNIT SHOWING |
| COMPLIANCE WITH THE REQUIREMENTS OF THE FAIR HOUSING |
| ACCESSIBILITY GUIDELINES 24 CFR 100.205. SHOW ALL |
| REQUIRED CLEAR FLOOR SPACES AT PLUMBING FIXTURES AND |
| SHOW THE DIMENSIONS (LXW) OF THE CLEAR FLOOR SPACES. |
| 2) INDICATE ON THE FLOOR PLAN FOR THE "G" UNIT WHAT |
| DESIGN SPECIFICATION ("A" OR "B") FROM THE FHAG IS |
| BEING USED FOR THE BATHROOMS IN THE "G" UNIT. |
| 3) CLEARLY SHOW ON THE FLOOR PLAN FOR THE UNIT WHICH |
| BATHROOM(S) IS THE FHAG COMPLIANT BATHROOM(S).WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 4) PROVIDE A SANITARY AND WATER RISER DIAGRAM FOR THE |
| "G" UNIT. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 5) SHT. P104B - THE TEXT IN THE LOWER RIGHT HAND CORNER |
| CALLS OUT A "B" FLOOR PLAN BUT THE UNITS ARE ALL SHOWN |
| AS "C" UNITS ON THE PLAN. CLARIFY. |
| 6) SHT.P210A - THE NARRATIVE REFERS TO A HOT WATER |
| RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE |
| LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 7) SHT. 210B - THE NARRATIVE REFERS TO A HOT WATER |
| RETURN LINE ON THE TENTH FLOOR. CLEARLY IDENTIFY THE |
| LOCATION OF THE HWR LINE ON THE PLAN BY CLOUDING. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |