Plan Review Notes
Plan Review Notes For Permit 17060343
Permit Number 17060343
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-28 07:36:584850 LORING DRIVE
 TRACKING #17060343
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET G101:
  
 1) NEW 3-HOUR FIRE WALL WITH SLIDING FIRE DOOR IS ALSO
 IDENTIFIED ON THE PLAN AS "1-HOUR FIRE BARRIER
 OCCUPANCY SEPARATION."
 2) SUBMIT PRODUCT DATA FOR NEW 3-HOUR SLIDING FIRE
 DOOR. DOORS IN ASSEMBLY OCCUPANCIES ARE REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS (NORTH) AND BE
 EQUIPPED WITH PANIC/FIRE EXIT HARDWARE. HOW WILL THIS
 BE ACCOMPLISHED WITH THE SLIDING FIRE DOOR?
 3) AN ADDITIONAL EXIT SIGN IS NEEDED ON THE SOUTH SIDE
 OF THE 3-HOUR FIRE DOOR NOW THAT THE CLOSEST EXIT SIGN
 WILL BE OBSTRUCTED BY THE NEW DOOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  