2017-06-26 09:26:09 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. FBC 107, THE TRANSMITTAL LETTER STATES THAT A |
| NARRATIVE IS INCLUDED BUT I WAS UNABLE TO LOCATE A |
| NARRATIVE FOR BUILDING, ONLY PLUMBING. DUE TO THE |
| SIGNIFICANT NATURE OF THIS REVISION, AND DUE TO THE |
| FACT THAT THE CHANGE AND THE REASON FOR THE CHANGE ARE |
| NOT EASILY DETERMINED BY SOMEONE UNFAMILIAR WITH THE |
| PROJECT, PLEASE PROVIDE A DETAILED NARRATIVE. |
| |
| 2. A101C, (AS AN EXAMPLE; APPLIES TO OTHER SHEETS) THE |
| LAST REVIEWED SHEET WAS REVISION NO 20 DATED 9/30/16. |
| THREE REVISIONS ARE SHOWN (28,29,30) AND NOT ALL |
| CHANGES ARE CLOUDED. NARRATIVE SHOULD BE CLEAR AS TO |
| CHANGES, CHANGES SHOULD BE INDICATED ON EACH PAGES. |
| |
| 2. FBC 2010 706.5.1, REVISE PLAN TO SHOW COMPLIANCE |
| WITH ONE OF THE OPTIONS. THE PROPOSED NEW L-SHAPED 3 |
| HOUR FIRE WALL INTERSECTS TWO EXTERIOR WALLS. |
| |
| 3. FBC 2010 706.5.2, REVISE PLAN TO INDICATE WHETHER OR |
| NOT HORIZONTAL PROJECTION ELEMENTS ARE AFFECTED BY THIS |
| CHANGE. |
| |
| 4. REVISE OTHER SHEETS AFFECTED BY THIS CHANGE; SUCH AS |
| G001. |
| |
| 5. WALL ID TAGS DO NOT APPEAR TO HAVE BEEN REVISED TO |
| REFLECT THE CHANGE FROM A 1 HOUR PARTITION OR BARRIER |
| AND AN UNRATED WALL TO A 3 HOUR FIRE WALL. THE EXTERIOR |
| PORTION OF THE PROPOSED NEW 3 HOUR FIRE WALL LACKS A |
| WALL TAG, FBC 107, FBC 706. THE DETAIL FOR WALL TYPE N |
| DOES NOT INCLUDE A 3 HOUR RATING, WALL TYPE P IS NOT A |
| RATED WALL. REVISE DETAILS AND WALL TAGS TO SHOW A 3 |
| HOUR WALL WHERE ONE IS PROPOSED. IT APPEARS THAT OTHER |
| (PORTION OF) WALLS ALSO REQUIRE A RATING WHERE THEY |
| INTERSECT THE 3 HOUR WALL, SEE OTHER COMMENTS. |
| |
| A102A, STAIR 1 SHOWS AN UNRATED WALL, ISN'T THIS AN |
| EXIT STAIR WITH A 2 HOUR REQUIREMENT? STAIRS 1 AND 2 |
| APPEAR TO SHOW A 0 RATING, BUT ELEVATOR 2-2 APPEARS TO |
| SHOW A 2 HOUR REQUIREMNT. FBC 107, CLARIFY AND REVISE |
| WALL ID TAGS AS NECESSARY. |
| |
| 6. PROVIDE A SUMMARY OF UNIT DESIGNATION NAME CHANGES |
| (A COLUMN WITH THE OLD UNIT NUMBER, A COLUMN WITH THE |
| CORRESPONDING NEW UNIT NUMBER), FBC 107. PAGES WHICH |
| WERE AFFECTED BY THE CHANGE WHICH WERE NOT REVISED WILL |
| BE COVERED UNDER THIS SUMMARY PAGE. |
| |
| |