Plan Review Notes
Plan Review Notes For Permit 17060343
Permit Number 17060343
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-26 09:26:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, THE TRANSMITTAL LETTER STATES THAT A
 NARRATIVE IS INCLUDED BUT I WAS UNABLE TO LOCATE A
 NARRATIVE FOR BUILDING, ONLY PLUMBING. DUE TO THE
 SIGNIFICANT NATURE OF THIS REVISION, AND DUE TO THE
 FACT THAT THE CHANGE AND THE REASON FOR THE CHANGE ARE
 NOT EASILY DETERMINED BY SOMEONE UNFAMILIAR WITH THE
 PROJECT, PLEASE PROVIDE A DETAILED NARRATIVE.
  
 2. A101C, (AS AN EXAMPLE; APPLIES TO OTHER SHEETS) THE
 LAST REVIEWED SHEET WAS REVISION NO 20 DATED 9/30/16.
 THREE REVISIONS ARE SHOWN (28,29,30) AND NOT ALL
 CHANGES ARE CLOUDED. NARRATIVE SHOULD BE CLEAR AS TO
 CHANGES, CHANGES SHOULD BE INDICATED ON EACH PAGES.
  
 2. FBC 2010 706.5.1, REVISE PLAN TO SHOW COMPLIANCE
 WITH ONE OF THE OPTIONS. THE PROPOSED NEW L-SHAPED 3
 HOUR FIRE WALL INTERSECTS TWO EXTERIOR WALLS.
  
 3. FBC 2010 706.5.2, REVISE PLAN TO INDICATE WHETHER OR
 NOT HORIZONTAL PROJECTION ELEMENTS ARE AFFECTED BY THIS
 CHANGE.
  
 4. REVISE OTHER SHEETS AFFECTED BY THIS CHANGE; SUCH AS
 G001.
  
 5. WALL ID TAGS DO NOT APPEAR TO HAVE BEEN REVISED TO
 REFLECT THE CHANGE FROM A 1 HOUR PARTITION OR BARRIER
 AND AN UNRATED WALL TO A 3 HOUR FIRE WALL. THE EXTERIOR
 PORTION OF THE PROPOSED NEW 3 HOUR FIRE WALL LACKS A
 WALL TAG, FBC 107, FBC 706. THE DETAIL FOR WALL TYPE N
 DOES NOT INCLUDE A 3 HOUR RATING, WALL TYPE P IS NOT A
 RATED WALL. REVISE DETAILS AND WALL TAGS TO SHOW A 3
 HOUR WALL WHERE ONE IS PROPOSED. IT APPEARS THAT OTHER
 (PORTION OF) WALLS ALSO REQUIRE A RATING WHERE THEY
 INTERSECT THE 3 HOUR WALL, SEE OTHER COMMENTS.
  
 A102A, STAIR 1 SHOWS AN UNRATED WALL, ISN'T THIS AN
 EXIT STAIR WITH A 2 HOUR REQUIREMENT? STAIRS 1 AND 2
 APPEAR TO SHOW A 0 RATING, BUT ELEVATOR 2-2 APPEARS TO
 SHOW A 2 HOUR REQUIREMNT. FBC 107, CLARIFY AND REVISE
 WALL ID TAGS AS NECESSARY.
  
 6. PROVIDE A SUMMARY OF UNIT DESIGNATION NAME CHANGES
 (A COLUMN WITH THE OLD UNIT NUMBER, A COLUMN WITH THE
 CORRESPONDING NEW UNIT NUMBER), FBC 107. PAGES WHICH
 WERE AFFECTED BY THE CHANGE WHICH WERE NOT REVISED WILL
 BE COVERED UNDER THIS SUMMARY PAGE.
  
  