Plan Review Notes
Plan Review Notes For Permit 17060339
Permit Number 17060339
Review Stop G
Sequence Number 1
Notes
Date Text
2017-06-15 06:53:231) THE GAS PERMIT APPLICATION STATES THAT THE GAS METER
 IS EXISTING YET THE SURVEY AND THE WORK ORDER NOTES THE
 METER AS NEW. CLARIFY.
 2) THE SURVEY SHOWS A BBQ WHICH I AM ASSUMING IS GAS
 BUT THE GAS DRAWING DOES NOT SHOW THE BBQ. CLARIFY.
 3) SUBMIT A COPY OF THE LOW PRESSURE SIZING TABLE BEING
 USED FOR THE SCH. 40 METALLIC PIPE OR REFERENCE THE
 SPECIFIC SIZING TABLE ON BOTH SETS OF PLANS. 2014 FBCR
 SEC.G2413.3.
 4) SHOW THE DISTANCE OF THE GENERATOR FROM THE
 BUILDING.COMPLY WITH NFPA 37, SEC.4.1.2.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  