2017-08-11 13:21:21 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. G101, THE PROPOSED NEW 3 HOUR WALL IS NOT SHOWN ON |
| THIS PLAN. REVISE TO INCLUDE, AND ALSO INCLUDE ANY |
| OTHER RATINGS REQUIRED DUE TO INTERSECTION, SEE |
| COMMENTS FOR 17060343. |
| |
| 2ND REVIEW, RATING DUE TO INTERSECTION IS NOT SHOWN. I |
| CHECKED SHEET G101 FILED WITH REVISION 17060343 WHICH |
| WAS SUBMITTED ON THE SAME DAY, AND WAS GOING TO VOID |
| THE SHEET FILED WITH THIS REVISION IF THE OTHER ONE HAD |
| THE REQUESTED CHANGE. HOWEVER, THERE IS ANOTHER ISSUE |
| WITH THIS PAGE WHICH AFFECTS BOTH REVISIONS. |
| |
| SHEET G101 SUBMITTED WITH REVISION NUMBER 17060343 IS |
| SIGNED & SEALED DATED 7/2/17. IT INCLUDES REVISIONS |
| 1,2,4,5,10,30 AND 32 DATED 6/6/17. |
| |
| SHEET G101 SUBMITTED WITH REVISION NUMBER 17060328 IS |
| SIGNED & SEALED DATED 7/2/17. IT INCLUDES REVISIONS 1, |
| 10, AND 11. |
| |
| IT IS NOT CLEAR WHY ONE IS UP TO REVISION 32 AND HAS AN |
| EARLIER DATE THAN THE ONE WHICH INCLUDES REVISION 11. |
| WHY IS REVISION 11 NOT INCLUDED IN THE VERSION |
| SUBMITTED WITH 17060343? WHY DID THE ARCHITECT SIGN AND |
| SEAL TWO DIFFERENT SHEETS G101? (THESE ARE HYPOTHETICAL |
| QUESTIONS, NO NEED TO RESPOND IN WRITING.) |
| |
| PLEASE CORRELATE. IT IS OK, BUT NOT PREFERABLE, FOR THE |
| SAME SHEET TO BE SUBMITTED WITH TWO DIFFERENT |
| REVISIONS, BUT THEY DO NEED TO BE THE SAME. BOTH SHEETS |
| SHOULD BE THE SAME AND INCLUDE ALL INFORMATION WHICH |
| WAS INCORPORATED INTO ALL REVISIONS. |
| |
| PLEASE VERIFY THAT OTHER SHEETS ARE ALSO CONSISTENT. |
| |
| 2-3. OK |
| |