2017-08-15 16:03:15 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060297 |
| ADD: 222 LAKEVIEW AVE. UNIT: 3N |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-358-4439 |
| E-MAIL: ???????????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| 3RD REVIEW |
| DATE: TUES. AUGUST 15/2017 |
| ACTION: BUILDING PROVISO |
| |
| 1) BUILDING PROVISO: SHEET A-1 SHOWS THE USE OF BOTH |
| CERAMIC TILE AND WOOD FLOORS. BLDG TYPE: TYPE I/ TYPE |
| II FLOOR INSULATION (FBC-B 2014) FOR TILE, STONE, |
| MARBLE AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES FOR EACH |
| APPLICATION TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014 |
| 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 492. |
| |
| 1B) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014 |
| 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. |
| |
| 1C) BUILDING PROVISO/ DEFERRED SUBMITTAL: FLAME SPREAD- |
| FBC-B 2014 603.1. EXCEPTION 2. INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |