2017-07-21 07:06:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060297
 ADD: 222 LAKEVIEW AVE. UNIT: 3N
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-358-4439
 E-MAIL: ????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 21/2017
 ACTION: DENIED
  
 1) THE DOLLAR AMOUNT LISTED UNDER THE CONTRACT VALUE
 APPEARS TO BE LOW. ONCE THE CONTRACTOR HAS BEEN
 DETERMINED AND DOLLAR AMOUNT VERIFIED. 108.3* BUILDING
 PERMIT VALUATION.
  
 2) COMPLIED. TYPE IA CONSTRUCTION.
  
 3) 2ND REQUEST. THE LS-1 SHEET LISTS THE OCCUPANCIES
 FOR THIS UNIT AS BUSINESS & RESIDENTIAL (RZ?). NEITHER
 SHEET D-1 NOR A-1 SHOW ANY PORTION OF THE UNIT AS A
 BUSINESS OCCUPANCY. PLEASE NOTE IF ANY PORTION OF THE
 PROPOSED RESIDENTIAL UNIT IS TO BE OFFERED TO THE
 PUBLIC AS AN OFFICE THEN THIS IS A WORK LIVE LOFT
 GOVERNED UNDER SECTION 419 OF THE FBC-B. IF THIS IS A
 SINGLE RESIDENTIAL UNIT FOR LONG TERM USE THEN IT IS
 CONSIDERED A R2 OCCUPANCY GROUP. SEE 310.4 OF THE 2014
 FBC-B.
  
 4) BUILDING PROVISO: SHEET A-1 SHOWS THE USE OF BOTH
 CERAMIC TILE AND WOOD FLOORS. BLDG TYPE: TYPE I/ TYPE
 II FLOOR INSULATION (FBC-B 2014) FOR TILE, STONE,
 MARBLE AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES FOR EACH
 APPLICATION TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 4A) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 4B) BUILDING PROVISO/ DEFERRED SUBMITTAL: FBC-B 2014
 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 4C) BUILDING PROVISO/ DEFERRED SUBMITTAL: FLAME SPREAD-
 FBC-B 2014 603.1. EXCEPTION 2. INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4D) PLEASE ALSO REVIEW FIRES NOTES THAT DEAL WITH THE
 EXTERIOR CONCRETE DECK WHERE NO FIRE SPRINKLERS ARE
 LOCATED AND THE REQUIREMENTS OF NFPA, WHICH ARE MORE
 RESTRICTIVE OF THE 2 CODES. 101.4.5 FIRE PREVENTION.
 THE DESIGNER OF RECORD COULD SUBMIT TO THE BUILDING
 OFFICIAL A REQUEST UNDER ALTERNATIVE MATERIALS, DESIGN
 AND METHODS OF CONSTRUCTION SECTION 104.11 OF THE 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 5)2ND REQUEST. EVEN IF GIVEN THE WORST CASE SCENARIO(
 AS INDICATED ON THE PLAN) ONE CAN?T EVEN REVIEW FOR
 WIND DESIGN PRESSURES IF THE UNKNOWN IS THE HEIGHT OF
 THE BUILDING, OTHERWISE WORST CASE SCENARIO IS A D
 EXPOSURE AND THE SQUARE FOOTAGE OF 10 SQ. FT. IN A WALL
 ZONE 5, THE PRESSURES IN THIS SITUATION ARE HIGHER THAN
 THE SUBMITTED PRODUCT APPROVAL. ADDITIONAL INFORMATION
 IS REQUIRED TO SEE IF THE PRODUCT APPROVAL WOULD MEET
 THE REQUIRED WIND SPEED AND ASSOCIATED PRESSURES.
  
 SHEET A-1 SHOWS THE NEW INSTALLATION OF SLIDING GLASS
 DOORS ON THE 18TH AND 19TH FLOORS. IN THIS SET OF PLANS
 THERE IS NO WIND DESIGN CRITERIA PROVIDED. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6A) COMPLIED.
  
 6B) 2ND REQUEST. SUBMITTED PRODUCT APPROVAL A
 MIAMI-DADE NOA 16-0629.10 PGT SGD-780 (TABLE 1 OR TABLE
 3 ) HAS NOT IDENTIFIED THE UNIT SIZES, TYPE OF GLAZING,
 ANCHOR TYPES AND SPACING, SILL RISER HEIGHT AND
 ASSOCIATED PRESSURES NOR THE PRESSURES ASSOCIATED WITH
 EACH GLAZING AND ANCHOR TYPE.
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1. INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 6C) 2ND REQUEST. 1710.5.1.1FBC-B EXTERIOR WINDOWS AND
 DOORS. (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE
 THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED
 NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG
 RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 6D) SEMI-COMPLIED. THE PRODUCT APPROVAL HAS THE STAMP
 OF ACCEPTANCE BUT NONE OF THE TABLES ARE FILED OUT
 SHOWING THE WIDTH OF THE DOOR, HEIGHT, SILL HEIGHT,
 ANCHORS GLAZING TYPE NOR ANCHORS TO PROVE CODE
 COMPLIANCE.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) COMPLIED.
  
 8) SHEET A-6 COMPLIED.
  
 8A) SEMI- COMPLIED. TREAD DEPTH IS GIVEN BUT NOT THE
 HEIGHT OF THE RISERS. 1009.7.4 DIMENSIONAL UNIFORMITY.
 STAIR TREADS AND RISERS SHALL BE OF UNIFORM SIZE AND
 SHAPE. THE TOLERANCE BETWEEN THE LARGEST AND SMALLEST
 RISER HEIGHT OR BETWEEN THE LARGEST AND SMALLEST TREAD
 DEPTH SHALL NOT EXCEED 3/8 INCH (9.5 MM) IN ANY FLIGHT
 OF STAIRS.
  
 8B-C) COMPLIED.
  
 9) COMPLIED.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER