Plan Review Notes
Plan Review Notes For Permit 17060297
Permit Number 17060297
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-15 12:58:401ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY RISER DIAGRAM IS EXTREMELY HARD TO
 FOLLOW PLEASE SUBMIT AN EXPANDED RISER THAT SHOWS EACH
 PIPE CLEARLY WITHOUT OVERLAPPING OTHER PIPES. PER WPB
 AMEND TO FBC 107.2.1
  
 2. THE HORIZONTAL PIPING FOR THE 18TH FLOOR BATHROOMS
 SHOW OPPOSING DIRECTION OF FLOW IF FITTINGS ARE SHOWN
 THEY SHALL ALL SHOW DIRECTION OF FLOOR TOWARDS SOIL
 STACK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE RISER ON THE18TH FLOOR SHOWS HORIZONTAL DRY
 VENTS FOR P-3 WHICH ARE NOT ALLOWED BY CODE. PER FBC PL
 905.3 AND 905.4
  
 4. PLEASE SHOW SOIL STACK COMING DOWN FROM 18TH FLOOR.
 PER WPB AMEND TO FBC
  
 5. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC PL 708.3.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  