2017-06-14 11:47:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 7 - THERE IS INDICATIONS OF NEW WOOD |
| FLOORING SYSTEM OVER THE BALCONY. |
| |
| PER NFPA 13, |
| |
| 8.15.7* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, |
| BALCONIES, DECKS, OR SIMILAR PROJECTIONS. |
| 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, |
| OR |
| 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, BALCONIES, |
| DECKS, OR SIMILAR PROJECTIONS EXCEEDING 4 FT (1.2 M) IN |
| WIDTH. |
| 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| WHERE THE CANOPIES, ROOFS, PORTE-COCHERES, BALCONIES, |
| DECKS, OR SIMILAR PROJECTIONS ARE CONSTRUCTED WITH |
| MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, |
| OR FIRE RETARDANT?TREATED |
| WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE |
| RETARDANTTREATED WOOD AND FIRE-RETARDANT COATINGS FOR |
| BUILDING MATERIALS. |
| 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| FROM BELOW THE CANOPIES, ROOFS, PORTE-COCHERES, |
| BALCONIES, DECKS, OR SIMILAR PROJECTIONS OF COMBUSTIBLE |
| CONSTRUCTION, PROVIDED THE EXPOSED FINISH MATERIAL ON |
| THE ROOFS, CANOPIES, OR PORTECOCHERES ARE |
| NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE RETARDANT |
| TREATED WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE |
| RETARDANT TREATED WOOD AND FIRE-RETARDANT COATINGS FOR |
| BUILDING MATERIALS, AND THE ROOFS, CANOPIES, OR |
| PORTE-COCHERES CONTAIN ONLY SPRINKLERED CONCEALED |
| SPACES OR ANY OF THE FOLLOWING UNSPRINKLERED |
| COMBUSTIBLE CONCEALED SPACES: |
| (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH |
| NONCOMBUSTIBLE INSULATION |
| (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE |
| NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE CEILINGS ARE |
| DIRECTLY ATTACHED TO THE BOTTOM OF SOLID WOOD JOISTS SO |
| AS TO CREATE ENCLOSED JOIST SPACES 160 FT3 (4.5 M3) OR |
| LESS IN VOLUME, INCLUDING SPACE BELOW INSULATION THAT |
| IS LAID DIRECTLY ON TOP OR WITHIN THE CEILING JOISTS IN |
| AN OTHERWISE SPRINKLERED ATTIC [SEE 11.2.3.1.4(4)(D)] |
| (3) CONCEALED SPACES OVER ISOLATED SMALL ROOFS, |
| CANOPIES, OR PORTE-COCHERES NOT EXCEEDING 55 FT2 (5.1 |
| M2) IN AREA |
| 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| FROM EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF |
| THE CORRIDOR ARE AT LEAST 50 PERCENT OPEN AND WHEN THE |
| CORRIDOR IS ENTIRELY OF NONCOMBUSTIBLE CONSTRUCTION. |
| 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER ROOFS, |
| CANOPIES, PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR |
| PROJECTIONS GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS |
| WHERE COMBUSTIBLES ARE STORED. |
| |
| THE PROPOSED WOOD DECKING IS NOT APPROVED FOR |
| INSTALLTION AND ANY INSTALLATION OF COMBUSTIBLE |
| MATERIALS SHALL MEET ALL THE REQUIREMENTS NOTED AND/OR |
| THE AREA SHALL BE PROTECTED WITH FIRE SPRINKLERS. |
| |
| PLEASE CORRECT OR DISCONTINUE THE PROPOSED. |
| |
| |
| |
| 2) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM |
| DEVICES. ANY FIRE ALARM WORK SHALL BE DONE UNDER |
| SEPARATE SHOP DRAWING BY CERTIFIED LIFE SAFETY |
| CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF INTENDED |
| COMPLIANCE. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |