2017-06-14 11:47:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 7 - THERE IS INDICATIONS OF NEW WOOD
 FLOORING SYSTEM OVER THE BALCONY.
  
 PER NFPA 13,
  
 8.15.7* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, BALCONIES,
 DECKS, OR SIMILAR PROJECTIONS EXCEEDING 4 FT (1.2 M) IN
 WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE CANOPIES, ROOFS, PORTE-COCHERES, BALCONIES,
 DECKS, OR SIMILAR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT?TREATED
 WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE
 RETARDANTTREATED WOOD AND FIRE-RETARDANT COATINGS FOR
 BUILDING MATERIALS.
 8.15.7.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW THE CANOPIES, ROOFS, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS OF COMBUSTIBLE
 CONSTRUCTION, PROVIDED THE EXPOSED FINISH MATERIAL ON
 THE ROOFS, CANOPIES, OR PORTECOCHERES ARE
 NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE RETARDANT
 TREATED WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE
 RETARDANT TREATED WOOD AND FIRE-RETARDANT COATINGS FOR
 BUILDING MATERIALS, AND THE ROOFS, CANOPIES, OR
 PORTE-COCHERES CONTAIN ONLY SPRINKLERED CONCEALED
 SPACES OR ANY OF THE FOLLOWING UNSPRINKLERED
 COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE CEILINGS ARE
 DIRECTLY ATTACHED TO THE BOTTOM OF SOLID WOOD JOISTS SO
 AS TO CREATE ENCLOSED JOIST SPACES 160 FT3 (4.5 M3) OR
 LESS IN VOLUME, INCLUDING SPACE BELOW INSULATION THAT
 IS LAID DIRECTLY ON TOP OR WITHIN THE CEILING JOISTS IN
 AN OTHERWISE SPRINKLERED ATTIC [SEE 11.2.3.1.4(4)(D)]
 (3) CONCEALED SPACES OVER ISOLATED SMALL ROOFS,
 CANOPIES, OR PORTE-COCHERES NOT EXCEEDING 55 FT2 (5.1
 M2) IN AREA
 8.15.7.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF
 THE CORRIDOR ARE AT LEAST 50 PERCENT OPEN AND WHEN THE
 CORRIDOR IS ENTIRELY OF NONCOMBUSTIBLE CONSTRUCTION.
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER ROOFS,
 CANOPIES, PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS
 WHERE COMBUSTIBLES ARE STORED.
  
 THE PROPOSED WOOD DECKING IS NOT APPROVED FOR
 INSTALLTION AND ANY INSTALLATION OF COMBUSTIBLE
 MATERIALS SHALL MEET ALL THE REQUIREMENTS NOTED AND/OR
 THE AREA SHALL BE PROTECTED WITH FIRE SPRINKLERS.
  
 PLEASE CORRECT OR DISCONTINUE THE PROPOSED.
  
  
  
 2) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES. ANY FIRE ALARM WORK SHALL BE DONE UNDER
 SEPARATE SHOP DRAWING BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF INTENDED
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL