2017-06-15 16:44:36 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| NFPA 70 2011 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| |
| 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| FOR PERSONNEL |
| |
| (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| SPECIFIED |
| IN 210.8(A)(1) THROUGH (10) SHALL HAVE GROUND-FAULT |
| CIRCUI T |
| INTERRUPTER PROTECTION FOR PERSONNEL. |
| (7) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 |
| M |
| (6 FT) OF THE OUTSIDE EDGE OF THE SINK |
| |
| 210.52 DWELLING UNIT RECEPTACLE OUTLETS |
| |
| (A) GENERAL PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM, |
| DINING |
| ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN, SUNROOM, |
| BEDROOM, RECREATION |
| ROOM, OR SIMILAR ROOM OR AREA OF DWELLING UNITS, |
| RECEPTACLE |
| OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| GENERAL PROVISIONS |
| SPECIFIED IN 210.52(A)(1) THROUGH (A)(4). |
| |
| (1) SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT |
| NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS |
| MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE OUTLET. |
| |
| (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE |
| SHALL |
| INCLUDE THE FOLLOWING: |
| (1) ANY SPACE 600 MM (2 F T) OR MORE IN WIDTH |
| (INCLUDING SPACE |
| MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR |
| LINE BY DOORWAYS AND SIMILAR OPENINGS, FIREPLACES, AND |
| FIXED CABINETS |
| (2) THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR |
| WALLS, |
| EXCLUDING SLIDING PANELS |
| (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS |
| FREESTANDING |
| BAR-TYPE COUNTERS OR RAILINGS |
| |
| |
| 408. 4 FIELD IDENTIFICATION REQUIRED |
| (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY |
| CIRCUIT |
| AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS |
| TO |
| ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE |
| IDENTIFICATION |
| SHALL INCLUDE AN APPROVED DEGREE OF DETAIL THAT ALLOWS |
| EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE |
| POSITIONS |
| THAT CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES |
| SHALL BE |
| DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| INCLUDED IN |
| A CIRCUIT DIRECTORY THAT IS LOCATED ON THE FACE OR |
| INSIDE OF THE |
| PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH |
| SWITCH OR |
| CIRCUIT BREAKER IN A SWITCHBOARD OR SWITCHGEAR. NO |
| CIRCUIT SHALL |
| BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT |
| CONDITIONS |
| OF OCCUPANCY. |