2017-08-28 17:49:172ND REVIEW: FBC 2014 5TH EDITION
  
 PREVIOUS COMMENT NOT COMPLIED1. PLUMBING COMMENTS: THE
 BREAKROOM/ KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2
 AND 606.3
  
 PREVIOUS COMMENT NOT COMPLIED 2. THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE. PER FBC
 ACC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 NEW COMMENT
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW. FBC ACC 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  