2017-06-29 16:59:591ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060278
 6/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A NON-COMBUSTIBLE DOOR IS REQUIRED FOR THE AC
 CLOSET. SHEET A901 INDICATES A WOOD-LOUVERED DOOR- SEE
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION & SECTION
 602.2.1 FBC-14 MECHANICAL.
  
 2) VERIFY THE O/A INTAKE OPENING IS IN COMPLIANCE WITH
 SECTIONS 401.4 AND 401.5.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW CONDENSER TO THE EXISTING AC ROOF STANDS. IF
 SUBMITTING AN NOA PLEASE CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL APPLICABLE DESIGN PRESSURES,
 DETAILS, AND FASTENERS.
  