Plan Review Notes
Plan Review Notes For Permit 17060278
Permit Number 17060278
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-22 10:46:04CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ACCURATE LOAD CALCULATION. THE CURRENT LOAD
 CALCULATION USES THE SMALLER OF THE NON-CONCURRENT
 LOAD, CODE REQUIRES THE USE OF THE LARGEST OF THE TWO
 LOADS. NEC 220.60
 2. PROVIDE DETAILS OF ALL CIRCUITS WIRED THROUGH THE
 LIGHTING CONTROL PANEL TO COMPLY WITH LIGHTING AND
 RECEPTACLE CONTROL PER THE NOTES ON PLAN. FBC 107.2.1
 3. PLAN SHOWS THAT BOTH ELECTRICAL ROOMS ARE FED FROM
 THE SAME MAIN, MAIN #5. PROVIDE LOAD CALCULATION FOR
 THE MAIN SERVICE TO SHOW SUFFICIENT SIZE FOR THE
 ADDITIONAL LOAD. NEC 220
 4. PROVIDE SHORT CIRCUIT CALCULATION AT
 METER/DISCONNECT TO CONFIRM AIC SIZING REQUIREMENT OF
 SERVICE EQUIPMENT. NEC 110.9, 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  