2017-06-22 10:46:04 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION. THE CURRENT LOAD |
| CALCULATION USES THE SMALLER OF THE NON-CONCURRENT |
| LOAD, CODE REQUIRES THE USE OF THE LARGEST OF THE TWO |
| LOADS. NEC 220.60 |
| 2. PROVIDE DETAILS OF ALL CIRCUITS WIRED THROUGH THE |
| LIGHTING CONTROL PANEL TO COMPLY WITH LIGHTING AND |
| RECEPTACLE CONTROL PER THE NOTES ON PLAN. FBC 107.2.1 |
| 3. PLAN SHOWS THAT BOTH ELECTRICAL ROOMS ARE FED FROM |
| THE SAME MAIN, MAIN #5. PROVIDE LOAD CALCULATION FOR |
| THE MAIN SERVICE TO SHOW SUFFICIENT SIZE FOR THE |
| ADDITIONAL LOAD. NEC 220 |
| 4. PROVIDE SHORT CIRCUIT CALCULATION AT |
| METER/DISCONNECT TO CONFIRM AIC SIZING REQUIREMENT OF |
| SERVICE EQUIPMENT. NEC 110.9, 110.10 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |