2017-11-28 16:03:16 | RESIDENTIAL (R3) ADDITION/ALTERATION SIXTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO: PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED |
| INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY |
| INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO |
| ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| REVISION FEES APPLY IF INFORMATION IS SUBMITTED AFTER |
| THE PERMIT IS ISSUED. |
| |
| NEW COMMENT: |
| 1- EQUIPMENT SPECIFIED ON THE NEW ENERGY CALCULATIONS |
| SUBMITTED DOESN'T MATCH EQUIPMENT SHOWN ON THE A/C PLAN |
| SUBMITTED. EQUIPMENT SIZE AND MANUFACTURER DON'T MATCH. |
| REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| NOTE: COORDINATE WITH EQUIPMENT CALCULATIONS REQUESTED |
| ON THE MECHANICAL REVIEW. SEE MECHANICAL REVIEW |
| COMMENTS. |
| |
| 2- NEW ENERGY CALCULATIONS FORM 405-2014 SUBMITTED: |
| ORIGINAL COMMENT: |
| A) PERSON PREPARING THE ENERGY CALCULATIONS IS TAKING |
| THE "WHOLE HOUSE FAN OPTION". IN ORDER TO TAKE THIS |
| CREDIT THE REQUIREMENTS OF SEC. R405.7.5 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014) MUST BE MET. |
| ARCHITECTURAL PLANS DON'T SHOW ANY INFORMATION FOR |
| WHOLE HOUSE FAN. PERSON PREPARING THE ENERGY |
| CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THESE REQUIREMENTS ARE MET. |
| RESPONSE: |
| IT LOOKS LIKE THE ENERGY CALCULATIONS WERE REVISED BUT |
| THE ENERGY CALCULATIONS WERE NOT RESUBMITTED IN ITS |
| ENTIRETY. ONLY A COUPLE OF PAGES WERE RESUBMITTED. |
| SUBMIT 2 COPIES OF COMPLETE REVISED ENERGY |
| CALCULATIONS. |
| |
| ORIGINAL COMMENT: |
| B) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| PLANS. CLARIFY WHICH INSULATED DOORS ARE LOCATED EAST |
| AND WEST. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT |
| APPROVALS SUBMITTED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| RESPONSE: |
| CALCULATIONS WERE REVISED BUT THEY DON'T MATCH PLANS. |
| WHICH 36"X80" INSULATED DOOR IS LOCATED IN THE SOUTH |
| WALL?. AND, WHICH 26"X80" INSULATED DOOR IS LOCATED IN |
| THE NORTH WALL?. NOTE: ONLY THE DOORS THAT SEPARATE A/C |
| AREA FROM NON A/C AREA ARE THE ONES TO BE CONSIDERED. |
| |
| 2- TRUSS PACKAGE SUBMITTED; |
| A) ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| TRUSS PACKAGE BEFORE SUBMITTAL TO THIS OFFICE. SEC. |
| 107.3.4.2 CITY AMENDMENTS. |
| RESPONSE: |
| SHOP DRAWINGS REVIEW STAMP IS MISSING THE ARCHITECT'S |
| INFORMATION. IT DOESN'T IDENTIFY WHO REVIEW THE TRUSS |
| PACKAGE. PROVIDE SHOP DRAWINGS REVIEW STAMP THAT |
| INCLUDES THE ARCHITECT'S INFORMATION. |
| |
| |