Plan Review Notes For Permit 17060265 |
Permit Number |
17060265 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2017-12-15 18:06:25 | RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH MECHANICAL | | REVIEW CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | NOTE: ON PREVIOUS REVIEWS THE PROVISO OPTION WAS | | OFFERED. UNFORTUNATELY, RE-SUBMITTALS ARE RAISING MORE | | QUESTIONS THAN ANSWERS, THEREFORE DELAYING THE PERMIT | | PROCESS. | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED | | ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY | | CONSERVATION. | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | | 2- ARCHITECT OF RECORD TO SIGN AND SEAL BOTH A/C PLANS | | SUBMITTED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE | | WHEN SUBMITTING PLANS FOR PUBLIC RECORDS. NOTE: ONLY | | ONE COPY WAS SIGNED AT THIS TIME. | | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | | | | NOTE: CONTRACTOR MAY PROVIDE COMPLETE INFORMATION UNDER | | A SEPARATE MECHANICAL PERMIT. ADVICE IF THIS OPTION IS | | PREFERRED AT HIS TIME. | | | | | | *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING | | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|