2017-11-06 11:24:30 | RESIDENTIAL (R3) ADDITION/ALTERATION FIFTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO: PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED |
| INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY |
| INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO |
| ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| REVISION FEES APPLY. |
| |
| |
| 1- NEW ENERGY CALCULATIONS FORM 405-2014 SUBMITTED: |
| A) PERSON PREPARING THE ENERGY CALCULATIONS IS TAKING |
| THE "WHOLE HOUSE FAN OPTION". IN ORDER TO TAKE THIS |
| CREDIT THE REQUIREMENTS OF SEC. R405.7.5 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014) MUST BE MET. |
| ARCHITECTURAL PLANS DON'T SHOW ANY INFORMATION FOR |
| WHOLE HOUSE FAN. PERSON PREPARING THE ENERGY |
| CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THESE REQUIREMENTS ARE MET. |
| NOTE: THIS INFORMATION IS ONLY REQUIRED WHEN THE ENERGY |
| CALCULATIONS ARE TAKING ANY CREDITS ON ITEM #15. |
| |
| B) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T MATCH |
| PLANS. CLARIFY WHICH INSULATED DOORS ARE LOCATED EAST |
| AND WEST. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT |
| APPROVALS SUBMITTED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T |
| MATCH PLANS. REVISE AS REQUIRED. REVISE WINDOWS |
| ORIENTATION AND SQUARE FOOTAGE TO MATCH PLANS AND |
| PRODUCT APPROVALS SUBMITTED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| NOTE: SEE SURVEY FOR CORRECT BUILDING ORIENTATION TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| 2- TYPICAL WALL SECTION @ FAMILY ROOM: PLANS WERE |
| REVISED TO BUILD A NEW ROOF OVER THE PROPOSED FAMILY |
| AREA ADDITION. SPECIFY ROOF VENTILATION AS REQUIRED BY |
| SEC. R806 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISED |
| WALL SECTION IS MISSING THIS INFORMATION. SPECIFY VENT |
| SIZE AND SPACING. |
| |
| 3- TRUSS PACKAGE SUBMITTED; |
| A) MISSING THE TRUSS LAYOUT. NOTE: TRUSS LAYOUT AND |
| ARCHITECT'S ROOF FRAMING PLAN NEED TO MATCH. SEC. |
| R301.1 FBC-RESIDENTIAL. PROVIDE TRUSS LAYOUT. |
| |
| B) ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| TRUSS PACKAGE BEFORE SUBMITTAL TO THIS OFFICE. SEC. |
| 107.3.4.2 CITY AMENDMENTS. |
| |