2017-11-29 08:01:56 | RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO: PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED |
| INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY |
| INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO |
| ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| REVISION FEES APPLY IF INFORMATION IS SUBMITTED AFTER |
| THE PERMIT IS ISSUED. |
| |
| NEW COMMENT: |
| 1- A) EQUIPMENT SIZE SPECIFIED ON THE A/C PLAN |
| SUBMITTED DOESN'T MATCH EQUIPMENT SIZE SPECIFIED ON THE |
| ENERGY CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO |
| MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B) EQUIPMENT SPECIFIED ON THE A/C PLAN SUBMITTED |
| DOESN'T MATCH EQUIPMENT SPECIFIED ON THE EQUIPMENT |
| SIZING CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO |
| MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| |
| 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED |
| ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION |
| OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| CONSERVATION. |
| |
| |
| 3- ARCHITECT OF RECORD TO SIGN AND SEAL BOTH A/C PLANS |
| SUBMITTED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE |
| WHEN SUBMITTING PLANS FOR PUBLIC RECORDS. NOTE: ONLY |
| ONE COPY WAS SIGNED AT THIS TIME. |
| |
| |
| NOTE: CONTRACTOR MAY PROVIDE COMPLETE INFORMATION UNDER |
| A SEPARATE MECHANICAL PERMIT. ADVICE IF THIS OPTION IS |
| PREFERRED AT HIS TIME. |
| |
| |
| *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |