2017-11-29 08:01:56RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO: PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED
 INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO
 ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME.
 REVISION FEES APPLY IF INFORMATION IS SUBMITTED AFTER
 THE PERMIT IS ISSUED.
  
 NEW COMMENT:
 1- A) EQUIPMENT SIZE SPECIFIED ON THE A/C PLAN
 SUBMITTED DOESN'T MATCH EQUIPMENT SIZE SPECIFIED ON THE
 ENERGY CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) EQUIPMENT SPECIFIED ON THE A/C PLAN SUBMITTED
 DOESN'T MATCH EQUIPMENT SPECIFIED ON THE EQUIPMENT
 SIZING CALCULATIONS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
  
 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION.
  
  
 3- ARCHITECT OF RECORD TO SIGN AND SEAL BOTH A/C PLANS
 SUBMITTED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE
 WHEN SUBMITTING PLANS FOR PUBLIC RECORDS. NOTE: ONLY
 ONE COPY WAS SIGNED AT THIS TIME.
  
  
 NOTE: CONTRACTOR MAY PROVIDE COMPLETE INFORMATION UNDER
 A SEPARATE MECHANICAL PERMIT. ADVICE IF THIS OPTION IS
 PREFERRED AT HIS TIME.
  
  
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  