2017-11-13 08:49:25 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| NFPA 70 2011 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| GARAGE DOES NOT SHOW ANY OUTLETS. CODE STATES: "AT |
| LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO THOSE FOR |
| SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH |
| BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH DETACHED |
| GARAGE OR ACCESSORY BUILDING WITH ELECTRIC POWER". |
| PROVIDE OUTLET. NEC 210.52(G); FBC RE3901.9 |
| |
| PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC |
| 210.8; FBC RE3902.2 |
| |
| PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| CODE. FBC R314.3, 315.1; FBC 107.2.1 |
| |
| PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| |
| |
| SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED |
| SO THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR |
| LINE OF ANY WALL SPACE IS MORE THAN 6 FEET FROM A |
| RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC 210.52; FBC |
| RE3901.2.1 |
| |
| THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE |
| STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS |
| CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| 210.52(C)(1); |
| FBC RE3901.4 |
| |
| E3903.2 HABITABLE ROOMS. AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN |
| EVERY HABITABLE |
| ROOM AND BATHROOM. [210.70(A)(1)] GARAGE AND NEW PORCH |
| |
| |