2017-10-02 11:31:59 | RESIDENTIAL (R3) ADDITION/ALTERATION FOURTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO: PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUIRED REVISED |
| INFORMATION AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY |
| INSPECTIONS TO AVOID CONFLICTS/DELAYS. CONTRACTOR TO |
| ADVICE IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| REVISION FEES APPLY. SIGN ENERGY CALCULATIONS. |
| |
| |
| 1- DIFFERENT ENERGY CALCULATIONS PRESCRIPTIVE FORM |
| R402-2014 SUBMITTED: |
| NOTE: PRESCRIPTIVE METHOD IS MORE STRICT THAN THE |
| PREVIOUS FORM R405-2014 SUBMITTED. NEED TO COMPLY WITH |
| ALL THE REQUIREMENTS OF TABLE R402A. THE FOLLOWING |
| CONDITIONS NEED TO BE MET: |
| A) THE PRESCRIPTIVE FORM R402-2014 CAN NOT BE USED IF |
| THE AIR HANDLER UNIT IS LOCATED IN THE ATTIC. SEE AIR |
| DISTRIBUTION INFORMATION ON TABLE R402A OF FORM |
| SUBMITTED. ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE |
| THE AIR HANDLER IS LOCATED IN THE ATTIC OF THE MAIN |
| HOUSE. CLEARLY IDENTIFY LOCATION OF AIR HANDLER UNIT. |
| |
| B) THE CONDITIONED FLOOR AREA SHOWN ON ITEM #5 NEEDS TO |
| BE REVISED. THE PROPOSED ADDITION IS 19'-9" X 12'-5". |
| THEREFORE THE CORRECT AREA IS =/- 245 S.F. NOT 208 S.F. |
| NOTE: ARCHITECTURAL PLANS NEED TO BE REVISED ALSO. |
| |
| C) THE WINDOWS U-FACTOR AND SHGC FACTOR SHOWN ON ITEM |
| #6 DON'T COMPLY WITH THE MIN. REQUIRED FACTORS SHOWN ON |
| TABLE R402A. SEE GENERAL INSTRUCTION #1 ON FRONT PAGE |
| OF FORM SUBMITTED AND REVISE AS REQUIRED. AND, PROVIDE |
| WINDOW AND DOORS MANUFACTURER'S SPECS SHOWING THAT THE |
| PROPOSED WINDOWS MEET THE REQUIRED FACTORS. |
| |
| D) THE CONCRETE BLOCK WALL INFORMATION SHOWN ON ITEM |
| #9(A)(2). CONCRETE BLOCK WALLS NEED TO HAVE INSULATION |
| ON THE INTERIOR AND EXTERIOR SIDE OF THE WALL AS |
| REQUIRED BY TABLE R402A . SEE NOTE #4 OF TABLE R402A. |
| PLANS DON'T SHOW ANY INSULATION ON THE INTERIOR AND |
| EXTERIOR SIDE OF THE WALL. PERSON PREPARING THE ENERGY |
| CALCULATIONS TO PROVIDE COMPLETE DOCUMENTATION SHOWING |
| COMPLIANCE WITH THIS REQUIREMENT. SEC. R103.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). REVISE AS |
| REQUIRED. |
| |
| E) THE CEILING INFORMATION ON ITEM 10 DOESN'T COMPLY |
| WITH TABLE R402A. THIS IS A SINGLE ASSEMBLY CEILING, |
| THERE IS NOT ATTIC AND THE MINIMUM CEILING INSULATION |
| REQUIRED BY TABLE R402A IS R-30. ALSO, ACCORDING TO |
| ARCHITECTURAL PLANS THE CEILING JOISTS ARE 2X6. IT |
| DOESN'T SEEM TO BE ENOUGH ROOM FOR THE R-30 INSULATION. |
| PROVIDE COMPLETE DETAILS L AND SPECIFICATIONS SHOWING |
| HOW INSTALLING R-30 INSULATION ON A 2X6 ROOF JOIST?. |
| SEC. R1074.2.1 CITY AMENDMENTS. ALSO, COORDINATE |
| CEILING AREA WITH ITEM #1(B) ABOVE. |
| |
| F) NEED TO COMPLETE THE MANDATORY REQUIREMENTS OF TABLE |
| R402B AS REQUIRED BY NOTE #3 OF THE GENERAL |
| INSTRUCTIONS OF FORM R402-2014 SUBMITTED. |
| |
| G) OWNER OR LEGALLY DESIGNATED AGENT NEED TO CERTIFY |
| AND DATE AT THE BOTTOM OF THE ENERGY CALCULATIONS |
| SUBMITTED AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| RESPONSE: REPEAT COMMENT. NEW FORM SUBMITTED WAS NOT |
| CERTIFIED AT THE BOTTOM OF THE FORM BY THE OWNER. |
| PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S |
| CERTIFICATION. |
| |
| NOTE: |
| LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS |
| REQUIRED WHEN CALCULATIONS ARE NO USING THE DEFAULT |
| FACTORS. |
| |
| |
| 2- THE "NEW PORCH ENCLOSURE" CONDITIONED FLOOR AREA |
| SHOWN ON THE AREA CALCULATIONS NEEDS TO BE REVISED. THE |
| PROPOSED "PORCH ENCLOSURE" ADDITION IS 19'-9" X 12'-5". |
| THEREFORE THE CORRECT AREA IS =/- 245 S.F. NOT 208 S.F. |
| NOTE: ARCHITECTURAL PLANS NEED TO BE REVISED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 3- TYPICAL WALL SECTION @ FAMILY ROOM: |
| A) SPECIFY CEILING INSULATION. SEC. R103.2 FBC-ENERGY |
| CONSERVATION. NOTE: KEEP IN MIND SIZE OF EXISTING ROOF |
| JOISTS (2X6). SPECIFY INSULATION TYPE AND R-VALUE. |
| ALSO, WALL SECTION SPECIFIES "EXISTING VENTED SOFFIT". |
| KEEP IN MIND THE CLEARANCE REQUIRED BETWEEN THE |
| INSULATION AND UNDERSIDE OF ROOF SHEATHING FOR CROSS |
| VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL, |
| 5TH EDITION (2014). |
| (REPEAT COMMENT). |
| |
| B) SPECIFY R-VALUE FOR CONCRETE BLOCK WALL INSULATION. |
| SEC. R103.2 FBC-ENERGY CONSERVATION. |
| (REPEAT COMMENT). |
| |
| C) PROVIDE SPECIFICATIONS FOR NEW CEILING FINISH THAT |
| IS COVERING THE INSULATION. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| NOTE: |
| ARCHITECT MAY BE CHARGED FOUR TIMES THE PLAN REVIEW |
| FEES FOR MULTIPLE REJECTIONS AS REQUIRED BY FLORIDA |
| STATUTE 553.80(2)(B) |
| |
| |