2017-08-28 09:24:41 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- ENERGY CALCULATIONS SUBMITTED (NOTE: ENERGY |
| CALCULATIONS AND PLANS NEED TO BE COORDINATED TO AVOID |
| CONFLICT/DELAYS): |
| A) OWNER OR LEGALLY DESIGNATED AGENT NEED TO CERTIFY |
| AND DATE AT THE BOTTOM OF THE ENERGY CALCULATIONS |
| SUBMITTED AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| B) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD SUBMITTED AS REQUIRED BY SEC. |
| R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) PLANS SUBMITTED DON'T SHOW ANY INFORMATION FOR THE |
| R-30 CEILING INSULATION (SPECIALLY ON THE FLAT ROOF OF |
| THE FAMILY AREA ADDITION) AND WALLS. PERSON PREPARING |
| THE ENERGY CALCULATIONS TO CLARIFY WHERE IS THIS |
| INFORMATION TAKEN FROM. NOTE: R-30 INSULATION MAY NOT |
| FIT IN THE FLAT ROOF OF THE NEW ADDITION. ALSO, PLANS |
| SUBMITTED DON'T SHOW ANY OVERHANG ON THE FLAT ROOF. |
| COORDINATE WITH ARCHITECT OF RECORD TO AVOID |
| CONFLICT/DELAYS AND REVISE AS REQUIRED. SEC. R103.2.1 |
| FBC-ENERGY CONSERVATION. |
| |
| D) PLANS SUBMITTED DON'T SHOW ANY INFORMATION FOR THE |
| CEILING VENTILATION ON THE FAMILY ADDITION AND GARAGE |
| ENCLOSURE. PERSON PREPARING THE ENERGY CALCULATIONS TO |
| CLARIFY WHERE IS THIS INFORMATION TAKEN FROM. ALSO, |
| PLANS SUBMITTED DON'T SHOW ANY OVERHANG ON THE FLAT |
| ROOF. COORDINATE WITH ARCHITECT OF RECORD TO AVOID |
| CONFLICT/DELAYS AND REVISE AS REQUIRED. SEC. R103.2.1 |
| FBC-ENERGY CONSERVATION. |
| |
| E) REVISE THE ROOF TYPE ON PAGE 2 OF 4. THE ROOF TYPE |
| IS GABLE NOT HIP. REVISE THE GABLE AREA AS WELL. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F) DOORS INFORMATION ON PAGE 3 OF 4 SPECIFY 3 INSULATED |
| DOORS. COORDINATE WITH PLANS AND PRODUCT APPROVALS AND |
| REVISE AS REQUIRED. NOTE: OVERHEAD GARAGE DOORS ARE NO |
| TO BE CONSIDERED. DOORS TO BE BE CONSIDERED ARE THOSE |
| THAT SEPARATE A/C SPACE FROM NON-A/C SPACE. REVISE AS |
| REQUIRED. |
| |
| NOTE: |
| LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS |
| REQUIRED WHEN CALCULATIONS ARE NO USING THE DEFAULT |
| FACTORS. |
| |
| 2- PLANS SUBMITTED NEED TO HAVE ARCHITECT'S ORIGINAL |
| SEAL AND SIGNATURE. PERMIT APPLICATION AND PLANS |
| SUBMITTED ARE HARD COPIES NOT DIGITAL SUBMITTAL. PLANS |
| SUBMITTED SHOW A DIGITAL SIGNATURE. THIS IS NOT ALLOWED |
| ON HARD COPIES SUBMITTAL. SEC. 481.221 F.S. |
| |
| 3- PROVIDE COMPLETE WALL SECTION THRU THE NEW FAMILY |
| ROOM ADDITION AND THRU THE NEW GARAGE ENCLOSURE. |
| SPECIFY ALL THE STRUCTURAL CONNECTIONS SHOWING |
| COMPLIANCE WITH THE LOAD PATH AS REQUIRED BY SEC. |
| R801.2, R601.2 AND R401.2 FBC-RESIDENTIAL. |
| RESPONSE. CLEARLY SPECIFY TYPE AND SIZE OF SIMPSON MTS |
| STRAP. SPECIFIED STRAP IS A WOOD TO WOOD CONNECTOR. |
| PROPOSED CONSTRUCTION LOOKS LIKE WOOD TO CONCRETE |
| BLOCK. SPECIFY SPACING OF STRAPS FROM WOOD BEAM TO |
| CONCRETE BLOCK BEAM. REVISE/CLARIFY DETAIL AS REQUIRED. |
| |
| 4- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE FAMILY |
| ROOM ADDITION. SEC. R301.1 FBC-RESIDENTIAL. SPECIFY ALL |
| FRAMING MEMBERS SIZES AND CONNECTORS. |
| RESPONSE. REPEAT COMMENT. THERE IS NO INFORMATION ABOUT |
| THE ROOF FRAMING SYSTEM AND CONNECTORS. SPECIFY FRAMING |
| MEMBERS SIZING, SPACING AND CONNECTORS TO VERIFY |
| COMPLIANCE WITH THE CURRENT WIND LOADS. NOTE: THIS AREA |
| WAS AN ENCLOSED PORCH. NOW IS PROPOSED TO BE LIVABLE |
| AREA. THAT'S WHY THE STRUCTURE NEEDS TO COMPLY WITH |
| CURRENT WIND LOADS. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED CALL FOR R-30 CEILING |
| INSULATION. PLANS NEED TO PROVIDE SPECIFICATIONS FOR |
| THE CEILING AND WALLS INSULATION AS REQUIRED BY SEC. |
| R103.1.1.2 FBC-ENERGY CONSERVATION. NOTE: KEEP IN MIND |
| THAT R-30 BUTT INSULATION IS ABOUT 9-1/2" THICK. SIZE |
| OF ROOF FRAMING MEMBERS MAY NOT ALLOW R-30 INSULATION |
| AND CROSS VENTILATION (IF VENTILATION IS SPECIFIED BY |
| THE ARCHITECT). COORDINATE WITH ITEM #4, ITEM #1(C) AND |
| #1(D) ABOVE. |
| |
| 6- SPECIFY ROOF VENTILATION FOR THE FAMILY ROOM |
| ADDITION AND GARAGE ENCLOSURE. SEC. R806.1 |
| FBC-RESIDENTIAL. |
| RESPONSE. REPEAT COMMENT. ENERGY CALCULATIONS AND PLANS |
| NEED TO BE COORDINATED TO AVOID CONFLICTS/DELAYS. |
| COORDINATE WITH ITEM #1(C) AND #1(D) ABOVE. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| THAT CORRESPONDS TO REPORT SUBMITTED. OR ARCHITECT TO |
| LIST THE CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT |
| TO EACH SPECIFIED CONNECTOR. |
| |
| 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| RESPONSE. |
| A) ARCHITECT'S LETTER SUBMITTED IS TOO GENERAL. IF |
| USING A LETTER AS A RESPONSE FOR THE REVIEW OF EACH |
| PRODUCT APPROVAL, THEN CLEARLY IDENTIFY EACH PRODUCT |
| APPROVAL BY MANUFACTURER'S NAME AND SPECIFIC NOA OR |
| FLORIDA PRODUCT APPROVAL NUMBER. |
| |
| B) LETTER SUBMITTED NEEDS ARCHITECT'S ORIGINAL SEAL AND |
| SIGNATURE. PERMIT APPLICATION AND PLANS SUBMITTED ARE |
| HARD COPIES NOT DIGITAL SUBMITTAL. LETTER SUBMITTED |
| SHOW A DIGITAL SIGNATURE. THIS IS NOT ALLOWED ON HARD |
| COPIES SUBMITTAL. SEC. 481.221 F.S. |
| |
| 9- NEW GARAGE DOOR PRODUCT APPROVAL SUBMITTED REQUIRES |
| 4.000 PSI MINIMUM CONCRETE JAMB. SEE NOA 14-0822.06 |
| SUBMITTED. REVISE GARAGE DOOR JAMB DETAILS AND |
| SPECIFICATIONS ON THE FLOOR PLAN AND DETAILS AS |
| REQUIRED BY THE NOA SUBMITTED. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |