2017-07-17 11:29:43RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 3- PLANS SUBMITTED ARE MISSING SHEET 2 OF 2. SEC.
 107.2.1 CITY AMENDMENTS. PROVIDE COMPLETE SET OF PLANS.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 4- SPECIFY CARBON MONOXIDE ALARMS BY ALL THE BEDROOMS
 AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 5- OPENING BETWEEN EXISTING BATHROOM AND PROPOSED
 GARAGE NEEDS TO COMPLY WITH THE OPENING PROTECTION AS
 REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL. REVISE PLANS
 SHOWING COMPLIANCE.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 6- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR FIRE
 SPECIFICATIONS AND SELF CLOSING DEVICE AS REQUIRED BY
 SEC. R302.5.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 7- EXISTING BATHROOM ADJACENT TO THE PROPOSED GARAGE
 NEEDS TO COMPLY WITH THE VENTILATION REQUIREMENTS OF
 SEC. R303.3 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS FOR
 THE VENTILATION. NOTE: COORDINATE WITH ITEM # 5 ABOVE.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 8- PROVIDE COMPLETE WALL SECTION THRU THE NEW FAMILY
 ROOM ADDITION AND THRU THE NEW GARAGE ENCLOSURE.
 SPECIFY ALL THE STRUCTURAL CONNECTIONS SHOWING
 COMPLIANCE WITH THE LOAD PATH AS REQUIRED BY SEC.
 R801.2, R601.2 AND R401.2 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 9- PROVIDE FOUNDATION PLAN FOR NEW FAMILY ROOM ADDITION
 AND PROPOSED GARAGE. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 10- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE FAMILY
 ROOM ADDITION. SEC. R301.1 FBC-RESIDENTIAL. SPECIFY ALL
 FRAMING MEMBERS SIZES AND CONNECTORS.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 11- SPECIFY ROOF VENTILATION FOR THE FAMILY ROOM
 ADDITION. SEC. R806.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 12- PROVIDE OVERHEAD GARAGE DOOR STRUCTURAL BUCK
 DETAIL. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 13- PROVIDE STRUCTURAL BUCK DETAIL FOR NEW FRENCH DOORS
 AND WINDOWS. SEC. R612..7.2.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) WINDOW MULLIONS AS SPECIFIED ON PLANS. NOTE:
 ARCHITECT OF RECORD TO SPECIFY MULLION SIZE TO BE USED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 C) ALL SIMPSON (OR ANY OTHER STRUCTURAL CONNECTOR)
 STRUCTURAL CONNECTORS SPECIFIED ON PLANS. PROVIDE ONLY
 THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR. OR ARCHITECT TO LIST
 THE CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 D) NEW OVERHEAD GARAGE DOOR THAT MEETS THE SIZE
 SPECIFIED ON PLANS. NOA 15-0225.06 SUBMITTED IS FOR
 GARAGE DOORS UP TO 9'-0" WIDE. SIZE OF DOOR SPECIFIED
 ON PLANS IS WIDER.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 15- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL THE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 16- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE
 NEW OPENING AND FRAMING FOR RELOCATED DOOR BETWEEN THE
 GARAGE AND KITCHEN AREA. SEC. R301.1 FBC-RESIDENTIAL.
 AND PROVIDE DETAIL./SPECS FOR CLOSING THE EXISTING DOOR
 OPENING.
 RESPONSE. REPEAT COMMENT. NOT ADDRESSED.
  
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  