Date |
Text |
2017-06-26 08:09:26 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THE DESIGN CERTIFICATION, PLAN PAGE A-1 REFERENCES |
| ENFORCEMENT BY THE CITY OF WELLINGTON BUILDING |
| DEPARTMENT. AUTHORITY HAVING JURISDITION (AHJ) IS THE |
| CITY OF WEST PALM BEACH, FL ENFORCING THE 2014 FLORIDA |
| BUILDING CODE W/2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION. PLEASE |
| CORRECT STATEMENT. |
| 2. PROVIDE ENERGY SUBMITTAL. |
| 3. ROOFING PERMIT REQUIRED, (APPLICATION ON-FILE). |
| PROVIDE ROOF FRAMING PLAN. SHOW CONNECTION DETAILS. |
| PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM |
| COMPONENTS. SPECIFY WOOD SPECIES AND PROPOSED SPANS OF |
| ROOF JOISTS. |
| 4. TYPICAL WALL SECTION DETAIL, PLAN PAGE A-1 SHOWS 2X6 |
| TOP PLATE WITH 2X4 WALL FRAMING. PLEASE CLARIFY. |
| 5. DESIGN CERTIFICATION FOR WIND LOAD COMPLIANCE STATES |
| " SEE FLOOR PLAN FOR WIND PRESSURES FOR WINDOWS AND |
| DOORS IN INTERIOR AND END ZONES". DESIGN WINDLOADS NOT |
| SPECIFIED ON FLOOR PLAN. PLEASE CLARIFY. |
| 6. SHOW LOCATION OF NEW A/C COMPRESSOR. IF ROOFTOP |
| APPLICATION IS SELECTED, PLEASE PROVIDE STRUCTURAL |
| FRAMING DETAIL. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY |
| SUBMITTAL COMPLIANT WITH FBC-E 103. |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| -OR- |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| |
| FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| GARAGE DOORS). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |
| |
| |