Plan Review Notes
Plan Review Notes For Permit 17060219
Permit Number 17060219
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-08 15:40:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020219
 ADD: 400 N. FLAGLER DR. SUITE: 2302
 CONT: PALM BEACH HURRICANE WINDOWS
 TEL: 561-678-8332
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 08/2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE ON THE FLOOR PLAN IF THIS IS AN END
 UNIT OR AN INTERIOR UNIT AWAY FROM THE CORNERS OF THE
 BUILDING. ADDITIONAL INFORMATION REQUIRED TO BE ABLE TO
 DETERMINE IF THE SLIDING GLASS DOORS ARE IN WALL END
 ZONE 5 OR WALL INTERIOR ZONE 4. PRESSURE WILL VARY
 DRASTICALLY! 107. 2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) PLEASE ALSO INDICATE THE SIZE OF THE OPENINGS 1 & 2.
 PROVIDE HOW MANY PANELS ARE GOING TO MAKE UP EACH
 OPENING. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3A) PLEASE ALSO INDICATE ON THE FLOOR PLAN IF THESE
 SLIDING GLASS DOORS ARE TO BE INSTALLED AT THE EDGE OF
 THE CONCRETE SLAB, OR SET BACK AWAY FROM THE EDGE
 MAKING A PORCH WITH OVERHANG. IF PORCH PLEASE PROVIDE
 HOW FAR BACK FROM THE EDGE OF THE SLAB WILL THE DOORS
 ARE INSTALLED? SEE FBC-B 1710.5.1.1 OVERHANG RATIOS FOR
 HABITABLE SPACES. DOOR ASSEMBLIES INSTALLED WHERE THE
 OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT
 BE TESTED FOR WATER INTRUSION.
  
 3B) SUBMITTED MIAMI-DADE NOA 15-1210.01. IN THE
 TECHNICAL SHEETS 7 OF 21 PROVIDES THE TABLE B1 SILL
 HEIGHTS PLEASE CIRCLE THE SILL TO BE INSTALLED FOR THIS
 INSTALLATION.
  
 4) SUBMITTED MIAMI-DADE NOA 15-1210.01. IN THE
 TECHNICAL SHEETS 7 OF 21 PROVIDES THE TABLE 1, IDENTIFY
 PANEL WIDTH, DOOR UNIT HEIGHT, TYPE OF GLAZING,
 ASSOCIATED PRESSURES & ANCHORS.
 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS
 SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  